Watlow EZ-ZONE
®
RMC Module 94 Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[`S2;B]
[ SZ.b]
Timer (1 to 4)
Source Zone B
Set the zone of the func-
tion selected above.
0 to 16 0 4330
[offset 50]
0x83 (131)
1 to 4
6
- - - - 31006 uint
RWES
[sas;b]
[SAS.b]
Timer (1 to 4)
Source Active State B
Set what state will be
read as on.
[high] High (37)
[LoW] Low (53)
High 4342
[offset 50]
0x83 (131)
1 to 4
0xC (12)
- - - - 31012 uint
RWES
[``ti]
[ ti]
Timer (1 to 4)
Time
Set the time span that
will be measured in
tenths of a second.
0 to 9,999.000 0.1 4344
[offset 50]
0x83 (131)
1 to 4
0xD (13)
224 31013 float
RWES
[`LEu]
[ LEv]
Timer (1 to 4)
Active Level
Set which output state
will indicate on.
[high] High (37)
[LoW] Low (53)
High 4346
[offset 50]
0x83 (131)
1 to 4
0xE (14)
- - - - 31014 uint
RWES
[`Ctr]
[`Set]
Counter Menu
[``Fn]
[ Fn]
Counter (1 to 4)
Function
Set whether the counter
increments or decre-
ments the count value.
Decrementing 0 returns
9,999. Incrementing
9,999 returns 0.
[``UP] Up (1456)
[``dn] Down (1457)
Up 4176
[offset 40]
0x82 (130)
1 to 4
9
- - - - 30009 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set