Watlow EZ-ZONE
®
RMC Module 49 Chapter 3 Operations Page
RMC Module • Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[`h;Er]
[ h.Er]
Current (1 to 4)
Heater Error
View the cause of the
most recent load fault
monitored by the cur-
rent transformer.
[nonE] None (61)
[high] High (37)
[Low] Low (53)
- - - - 1384
[offset 50]
0x73
(115)
1 to 4
3
- - - - 15003 uint
R
No Dis-
play
Current (1 to 4)
Actual Power
Power delivered to out-
put monitored by CT.
0.0 to 100.0% - - - - 1418
[offset 50]
0x73
(115)
1 to 4
0x14 (20)
- - - - 15020 float
R
No Dis-
play
Current (1 to 4)
Error Status
View the cause of the
most recent load fault
None (61)
Fail (32)
- - - - 1420
[offset 50]
0x73
(115)
1 to 4
21
- - - - 15021 uint
R
[`Lnr]
[oPEr]
Linearization Menu
[`Su;A]
[ Su.A]
Linearization (1 to 4)
Source Value A
View the value of
Source A.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - - 4526
[offset 70]
0x86
(134)
1 to 4
4
- - - - 34004 float
R
[oFSt]
[oFSt]
Linearization (1 to 4)
Offset
Set an offset to be ap-
plied to this function's
output.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0 4530
[offset 70]
0x86
(134)
1 to 4
6
- - - - 34006 float
RWES
[``o;u]
[ o.v]
Linearization (1 to 4)
Output Value
View the value of this
function's output.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - - 4532
[offset 70]
0x86
(134)
1 to 4
7
- - - - 34007 float
R
No Dis-
play
Linearization (1 to 4)
Error
View reported cause for
Linearization output
malfunction.
None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad calibration data (139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
- - - - 4574
[offset 70]
0x86
(134)
1 to 4
0x1C (28)
- - - - 34028 uint
R
[`CPE]
[oPEr]
Compare Menu
[`Su;A]
[ Su.A]
Compare (1 to 4)
Source Value A
View the value of
Source A.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - - 4012
[offset 40]
0x80
(128)
1 to 4
7
- - - - 28007 float
R
[`Su;b]
[ Su.b]
Compare (1 to 4)
Source Value B
View the value of
Source B.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - - 4014
[offset 40]
0x80
(128)
1 to 4
8
- - - - 28008 float
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0
and above.
R: Read
W: Write
E: EEPROM
S: User Set