Watlow EZ-ZONE
®
RMC Module 77 Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[A;tSP]
[A.tSP}
Control Loop (1 to 4)
Autotune Set Point **
Set the set point that
the autotune will use,
as a percentage of the
current set point.
50.0 to 200.0% 90.0
2258
[offset 70]
0x97
(151)
1 to 4
0x14 (20)
- - - - 8025 float
RWES
[t;Agr]
[t.Agr]
Control Loop (1 to 4)
Autotune Aggressive-
ness
Select the aggressive-
ness of the autotuning
calculations.
[Undr] Under damped (99)
[Crit] Critical damped (21)
[OuEr] Over damped (69)
Critical 2256
[offset 70]
0x97 (151)
1 to 4
0x13 (19)
- - - - 8024 uint
RWES
[`p;dl]
[ P.dL]
Control Loop (1 to 4)
Peltier Delay
Set a value that will
cause a delay when
switching from heat PID
mode to cool PID mode.
0.0 to 5.0 seconds 0.0 2274
[offset 70]
0x97 (151)
1 to 4
0x1C (28)
- - - - 8051 float
RWES
[`r;En]
[ r.En]
Control Loop (1 to 4)
Remote Set Point En-
able
Set whether this loop
will use a remote set
point.
[``no] No (59)
[`YES} Yes (106)
No 2540
[offset 80]
0x6B
(107)
1 to 4
0x15 (21)
48 7021 uint
RWES
[SFn;b]
[SFn.b]
Control Loop (1 to 4)
Source Function B
Set the function that
will provide the remote
set point.
[nonE] None (61)
[``Ai] Analog Input (142)
[CUrr] Current (22)
[`C;Pr] Cool Power, Control
Loop (161)
[`h;Pr] Heat Power, Control
Loop (160)
[PWr] Power, Control Loop (73)
[`Lnr] Linearization (238)
[MAt] Math (240)
[``Pu] Process Value (241)
[`SP;C] Set Point Closed, Con-
trol Loop (242)
[`SP;o] Set Point Open, Control
Loop (243)
[`uAr] Variable (245)
None 2544
[offset 80]
0x6B
(107)
1 to 4
0x17 (23)
- - - - 7023 uint
RWES
[`Si;B]
[ Si.b]
Control Loop (1 to 4)
Source Instance B
Set the instance of the
function selected above.
1 to 250 1 2546
[offset 80]
0x6B
(107)
1 to 4
0x18 (24)
- - - - 7024 uint
RWES
[`S2;b]
[ SZ.b]
Control Loop (1 to 4)
Source Zone B
Set the zone of the func-
tion selected above.
0 to 16 0 2550
[offset 80]
0x6B
(107)
1 to 4
0x1A (26)
- - - - 7026 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set