RMC Module • 69 • Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[p;unt]
[P.unt]
Process Value (1 - 4)
Pressure Units
If Process Value func-
tion is set for Pressure
to Altitude units, define
units of measure for con-
version.
[`psi] Pounds per Square Inch
(1671)
[pasc] Pascal (1674)
[atm] Atmosphere (1675)
[mbr] Millibar (1672)
[torr] Torr (1673)
PSI 3454
[offset 70]
0x7E
(126)
1 to 2
0x1C (28)
- - - - 26028 uint
RWES
[a;unt]
[A.unt]
Process Value (1 - 4)
Altitude Units
If Process Value func-
tion is set for Pressure
to Altitude units, define
units of measure for con-
version.
[`Hft] Kilofeet (1677)
[``ft] Feet (1676)
HFt 3456
[offset 70]
0x7E
(126)
1 to 2
0x1D (29)
- - - - 26029 uint
RWES
[`b;pr]
[ b.Pr]
Process Value (1 - 4)
Barometric Pressure
If Process Value function
is set for Wet Bulb / Dry
Bulb, define pressure
value used for humidity
calculation.
10.0 to 16.0 14.7 3458
[offset 70]
0x7E
(126)
1 to 2
0x1E (30)
- - - - 26030 float
RWES
[`Fil]
[ FiL]
Process Value (1 to 4)
Filter
Filtering smooths out
the output signal of this
function block. Increase
the time to increase fil-
tering.
0.0 to 60.0 seconds 0.0 3450
[offset 70]
0x7E
(126)
1 to 4
0x1A (26)
- - - - 26026 float
RWES
[`dio]
[`Set]
Digital Input/Output Menu
[`dir]
[ dir]
Digital Input/Output (7
to 12)
Direction
Set this function to
operate as an input or
output.
[OtPt] Output (68)
[``in] Input Voltage (193)
[iCon] Input Dry Contact (44)
Output 1200
[offset 30]
0x6A
(106)
7 to 12
1
82 6001 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set