Watlow EZ-ZONE
®
RMC Module 66 Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[``Pu]
[`Set]
Process Value Menu
[``Fn]
[ Fn]
Process Value (1 to 4)
Function
Set the function that
will be applied to the
source or sources.
[`oFF] Off (62)
[`S;bA] Sensor Backup (1201)
[`Aug] Average (1367)
[``C;o] Crossover (1368)
[`W;b] Wet Bulb Dry Bulb
(1369)
[``S;o] Switch Over (1370)
[diFF] Differential (1373)
[rAti] Ratio (1374)
[`add] Add (1375)
[MUL] Multiply (1376)
[A;diF] Absolute Difference
(1377)
[Min] Minimum (1378)
[MAH] Maximum (1379)
[root] Square Root (1380)
[usla] Vaisala (1648)
[`alt] Pressure to Altitude
(1649)
Off 3440
[offset 70]
0x7E
(126)
1 to 4
0x15 (21)
123 26021 uint
RWES
[SFn;A]
[SFn.A]
Process Value (1 to 4)
Source Function A
Set the type of function
that will be used for this
source.
[``Ai] Analog Input (142)
[``Pu] Process Value (241)
Analog
Input
3400
[offset 70]
0x7E
(126)
1 to 4
1
- - - - 26001 uint
RWES
[Si;A]
[ Si.A]
Process Value (1 to 4)
Source Instance A
Set the instance of the
function selected above.
1 to 250 3410
[offset 70]
0x7E
(126)
1 to 4
6
- - - - 26006 uint
RWES
[SFn;b]
[SFn.b]
Process Value (1 to 4)
Source Function B
Set the type of function
that will be used for this
source.
[nonE] None (61)
[``Ai] Analog Input, (142)
[`Lnr] Linearization (238)
[mat] Math (240)
[``Pu] Process Value (241)
[`uAr] Variable (245)
None 3402
[offset 70]
0x7E
(126)
1 to 4
2
- - - - 26002 uint
RWES
[`si;b]
[ Si.b]
Process Value (1 to 4)
Source Instance B
Set the instance of the
function selected above.
1 to 250 1 3412
[offset 70]
0x7E
(126)
1 to 4
7
- - - - 26007 uint
RWES
[`s2;b]
[ SZ.b]
Process Value (1 to 4)
Source Zone B
Set the zone of the func-
tion selected above.
0 to 16 0 3422
[offset 70]
0x7E
(126)
1 to 4
0xC(12)
- - - - 26012 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set