Watlow EZ-ZONE
®
RMC Module • 84 • Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[`S;hi]
[ S.hi]
Output Process (1, 3, 5
or 7)
Scale High
Set the scale high for
process output in electri-
cal units. This value, in
volts or milliamps, will
correspond to 0% PID
power output or the
range high value.
-100.0 to 100.0 10.00 858 (1)
906 (3)
954 (5)
1002 (7)
0x76 (118)
1 to 4
0xA (10)
100 18010 float
RWES
[`r;Lo]
[ r.Lo]
Output Process (1, 3, 5
or 7)
Range Low
Use to set the minimum
value in process units.
This will correspond
with the Scale Low
value.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18°C
860 (1)
908 (3)
956 (5)
1004 (7)
0x76 (118)
1 to 4
0xB (11)
101 18011 float
RWES
[`r;hi]
[ r.hi]
Output Process (1, 3, 5
or 7)
Range High
Use to set the maximum
value in process units.
This will correspond
with the Scale High
value.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
100 F or
units
38 C
862 (1)
910 (3)
958 (5)
1006 (7)
0x76 (118)
1 to 4
0xC (12)
102 18012 float
RWES
[`o;CA]
[ o.CA]
Output Process (1, 3, 5
or 7)
Calibration Offset
Set an offset value for a
process output.
-1,999.000 to 9,999.000°F or
units
-1,110.555 to 5,555.000°C
0.0°F or
units
0.0°C
852 (1)
900 (3)
948 (5)
996 (7)
0x76 (118)
1 to 4
7
105 18007 float
RWES
[Alm]
[`Set]
Alarm Menu
[`A;ty]
[ A.ty]
Alarm (1 to 8)
Type
Select whether the
alarm trigger is a fixed
value or will track the
set point.
[`oFF] Off (62)
[PR;AL] Process Alarm (76)
[dE;AL] Deviation Alarm (24)
Off 1768
[offset 60]
0x6D
(109)
1 to 8
0xF (15)
20 9015 uint
RWES
[`Sr;a]
[ Sr.A]
Alarm (1 to 8)
Source
Select what will trigger
this alarm.
[none] None (61)
[``Ai] Analog Input (142)
[CUrr] Current (22)
[PWr] Power (73)
[`Lnr] Linearization (238)
[MAt] Math (240)
[``Pu] Process Value (241)
[`uar] Variable (245)
[`Cu;r] Current Read (179)
Analog
Input
1772
[offset 60]
0x6D
(109)
1 to 8
0x11 (17)
21 9017 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set