Watlow EZ-ZONE
®
RMC Module • 51 • Chapter 3 Operations Page
RMC Module • Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[`Ctr]
[oPEr]
Counter Menu
[`Cnt]
[ Cnt]
Counter (1 to 4)
Count
View the function's to-
tal count.
0 to 9,999 - - - - 4188
[offset 40]
0x82
(130)
1 to 4
0xF (15)
217 30015 uint
R
[`Su;A]
[ Su.A]
Counter (1 to 4)
Source Value A
View the value of
Source A.
[`off] Off (62)
[``on] On (63)
- - - - 4172
[offset 40]
0x82
(130)
1 to 4
7
- - - - 30007 uint
R
[`Su;b]
[ Su.b]
Counter (1 to 4)
Source Value B
View the value of
Source B.
[`off] Off (62)
[``on] On (63)
- - - - 4174
[offset 40]
0x82
(130)
1 to 4
8
- - - - 30008 uint
R
[``o;u]
[ o.v]
Counter (1 to 4)
Output Value
View the value of this
function's output.
[`off] Off (62)
[``on] On (63)
- - - - 4178
[offset 40]
0x82
(130)
1 to 4
0xA (10)
- - - - 30010 uint
R
No Dis-
play
Counter (1 to 4)
Error
Read reported cause for
counter error
None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
- - - - 4190
[offset 40]
0x82
(130)
1 to 4
0x10 (16)
- - - - 30016 uint
R
[`LgC]
[oPEr]
Logic Menu
[`Su;A]
[ Su.A]
Logic (1 to 4)
Source Value A
View the value of
Source A.
[`off] Off (62)
[``on] On (63)
- - - - 3728
[offset 80]
0x7F
(127)
1 to 4
0x19 (25)
- - - - 27025 uint
R
[`Su;b]
[ Su.b]
Logic (1 to 4)
Source Value B
View the value of
Source B.
[`off] Off (62)
[``on] On (63)
- - - - 3730
[offset 80]
0x7F
(127)
1 to 4
0x1A (26)
- - - - 27026 uint
R
[`Su;C]
[ Su.C]
Logic (1 to 4)
Source Value C
View the value of
Source C.
[`off] Off (62)
[``on] On (63)
- - - - 3732
[offset 80]
0x7F
(127)
1 to 4
0x1B (27)
- - - - 27027 uint
R
[`Su;d]
[ Su.d]
Logic (1 to 4)
Source Value D
View the value of
Source D.
[`off] Off (62)
[``on] On (63)
- - - - 3734
[offset 80]
0x7F
(127)
1 to 4
0x1C (28)
- - - - 27028 uint
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0
and above.
R: Read
W: Write
E: EEPROM
S: User Set