Watlow EZ-ZONE
®
RMC Module 64 Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[`r;Lo]
[ r.Lo]
Analog Input (1 to 4)
Range Low
Set the low range for
this function block's
output.
-1,999.000 to 9,999.000 0.0 392
[offset 90]
0x68 (104)
1 to 4
0x11 (17)
8 4017 float
RWES
[`r;hi]
[ r.hi]
Analog Input (1 to 4)
Range High
Set the high range for
this function block's
output.
-1,999.000 to 9,999.000 9,999 394
[offset 90]
0x68 (104)
1 to 4
0x12 (18)
9 4018 float
RWES
[`P;EE]
[ P.EE]
Analog Input (1 to 4)
Process Error Enable
Turn the Process Error
Low feature on or off.
[`off] Off (62)
[Low] Low (53)
Off 418
[offset 90]
0x68 (104)
1 to 4
0x1E (30)
10 4030 uint
RWES
[`P;EL]
[ P.EL]
Analog Input (1 to 4)
Process Error Low
Value
If the process value
drops below this value,
it will trigger an input
error.
-100.0 to 1,000.0 0.0 420
[offset 90]
0x68 (104)
1 to 4
0x1F (31)
11 4031 float
RWES
[``t;C]
[ t.C]
Analog Input (1 to 4)
Thermistor Curve
Select a curve to apply
to the thermistor input.
[```A] Curve A (1451)
[```b] Curve B (1452)
[```C] Curve C (1453)
[CUSt] Custom (180)
Curve A 434
[offset 90]
0x68 (104)
1 to 4
0x26 (38)
- - - - 4038 uint
RWES
[``r;r]
[ r.r]
Analog Input (1 to 4)
Resistance Range
Set the maximum resis-
tance of the thermistor
input.
[```5] 5K (1448)
[``10] 10K (1360)
[``20] 20K (1361)
[``40] 40K (1449)
40K 432
[offset 90]
0x68 (104)
1 to 4
0x25 (37)
- - - - 4037 uint
RWES
[`FiL]
[ FiL]
Analog Input (1 to 4)
Filter
Filtering smooths out
the process signal to
both the display and the
input. Increase the time
to increase filtering.
0.0 to 60.0 seconds 0.5 386
[offset 90]
0x68 (104)
1 to 4
0xE (14)
12 4014 float
RWES
[`i;Er]
[ i.Er]
Analog Input (1 to 4)
Error Latching
Turn input error latch-
ing on or off. If latching
is on, errors must be
manually cleared.
[`off] Off (62)
[``on] On (63)
Off 414
[offset 90]
0x68 (104)
1 to 4
0x1C (28)
- - - - 4028 uint
RWES
[`dEC]
[ dEC]
Analog Input (1 to 4)
Display Precision
Set the precision of the
displayed value.
[```0] Whole (105)
[``0;0] Tenths (94)
[`0;00] Hundredths (40)
[0;000] Thousandths (96)
Whole 398
[offset 90]
0x68 (104)
1 to 4
0x14 (20)
- - - - 4020 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set