Watlow EZ-ZONE
®
RMC Module 76 Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[`C;hy]
[ C.hy]
Control Loop (1 to 4)
Cool Hysteresis **
Set the control switch-
ing hysteresis for on-off
control. This deter-
mines how far into the
“on” region the process
value needs to move
before the output turns
on.
0.001 to 9,999.000°F or units
0.001 to 5,555.000°C
3.0°F or
units
2.0°C
2242
[offset 70]
0x97
(151)
1 to 4
0xC (12)
68 8013 float
RWES
[``ti]
[ ti]
Control Loop (1 to 4)
Time Integral **
Set the PID integral for
the outputs.
0 to 9,999 seconds per repeat
180 sec-
onds per
repeat
2234
[offset 70]
0x97
(151)
1 to 4
8
69 8006 float
RWES
[``td]
[ td]
Control Loop (1 to 4)
Time Derivative **
Set the PID derivative
time for the outputs.
0 to 9,999 seconds 0
seconds
2236
[offset 70]
0x97
(151)
1 to 4
9
70 8007 float
RWES
[``dB]
[ db]
Control Loop (1 to 4)
Dead Band **
Set the offset to the
proportional band.
With a negative value,
both heating and cool-
ing outputs are active
when the process value
is near the set point.
A positive value keeps
heating and cooling
outputs from fighting
each other.
-1,000.0 to 1,000.0°F or units
-556 to 556°C
0.0
2238
[offset 70]
0x97
(151)
1 to 4
0xA (10)
71 8008 float
RWES
[t;tUn]
[t.tUn]
Control Loop (1 to 4)
TRU-TUNE+
®
Enable
Enable or disable the
TRU-TUNE+
®
adaptive
tuning feature.
[``no] No (59)
[`YES} Yes (106)
No
2250
[offset 70]
0x97 (151)
1 to 4
10 (16)
- - - - 8022 uint
RWES
[t;bnd]
[t.bnd]
Control Loop (1 to 4)
TRU-TUNE+
®
Band
Set the range, centered
on the set point, within
which TRU-TUNE+
®
will be in effect. Use this
function only if the con-
troller is unable to adap-
tive tune automatically.
0 to 100 0 2252
[offset 70]
0x97 (151)
1 to 4
0x11 (17)
- - - - 8034 uint
RWES
[`t;gn]
[ t.gn]
Control Loop (1 to 4)
TRU-TUNE+
®
Gain
Select the respon-
siveness of the TRU-
TUNE+
®
adaptive tun-
ing calculations. More
responsiveness may
increase overshoot.
1 to 6 3 2254
[offset 70]
0x97 (151)
1 to 4
0x12 (18)
- - - - 8035 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set