Watlow EZ-ZONE
®
RMC Module • 132 • Chapter 5 Profiling Page
RMC Module • Profile Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data Type
& Read/
Write
[WE;3]
[WE.3]
Step (1 to 250)
Wait Event 3
Select a state that
must be satisfied
which is specified by
Source C in Profile
Setup.
[nonE] None (61)
[``on] On (63)
[`oFF] Off (62)
None 5482
[offset 100]
0x79
(121)
1 to (250)
0x16 (22)
- - - - 21022 uint
RWE
[WE;4]
[WE.4]
Step (1 to 250)
Wait Event 4
Select a state that
must be satisfied
which is specified by
Source D in Profile
Setup.
[nonE] None (61)
[``on] On (63)
[`oFF] Off (62)
None 5484
[offset 100]
0x79
(121)
1 to (250)
0x18 (24)
- - - - 21024 uint
RWE
[dow]
[doW]
Step (1 to 250)
Day of Week
If step type is Wait
for Time, select day
of week for profile to
proceed.
[``Ed] Every Day (1567)
[`Wd] Week Days (1566)
[Mon] Monday (1559)
[`tue] Tuesday (1560)
[Wed] Wednesday (1561)
[thUr] Thursday (1562)
[`Fri] Friday (1563)
[`Sat] Saturday (1564)
[`sun] Sunday (1565)
Every
Day
5520
[offset 100]
0x79
(121)
1 to (250)
0x29 (41)
- - - - 21041 uint
RWE
[gSE1]
[gSE1]
Step (1 to 250)
Guaranteed Soak
Enable 1
Select if profile should
pause while process 1
deviates from devia-
tion band.
[`oFF] Off (62)
[``on] On (63)
Off 5522
[offset 100]
0x79
(121)
1 to (250)
0x2A (42)
- - - - 21042 uint
RWE
[gSE2]
[gSE2]
Step (1 to 250)
Guaranteed Soak
Enable 2
Select if profile should
pause while process 2
deviates from devia-
tion band.
[`oFF] Off (62)
[``on] On (63)
Off 5524
[offset 100]
0x79
(121)
1 to (250)
0x2B(43)
- - - - 21043 uint
RWE
[gSE3]
[gSE3]
Step (1 to 250)
Guaranteed Soak
Enable 3
Select if profile should
pause while process 3
deviates from devia-
tion band.
[`oFF] Off (62)
[``on] On (63)
Off 5526
[offset 100]
0x79
(121)
1 to (250)
0x2C (44)
- - - - 21044 uint
RWE
[gSE4]
[gSE4]
Step (1 to 250)
Guaranteed Soak
Enable 4
Select if profile should
pause while process 4
deviates from devia-
tion band.
[`oFF] Off (62)
[``on] On (63)
Off 5528
[offset 100]
0x79
(121)
1 to (250)
0x2D
(45)
- - - - 21045 uint
RWE
[``SS]
[ SS]
Step (1 to 250)
Subroutine Step
If step type is Sub-
routine, specify sub-
routine step to jump
to next.
1 to 15 1 5506
[offset 100]
0x79
(121)
1 to (250)
0x22 (34)
- - - - 21034 uint
RWE
Note: Some values will be rounded off to fit in the four-character display. Full values
can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User Set
Comentarios a estos manuales