Watlow EZ-ZONE RMC Manual de usuario Pagina 85

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 236
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 84
Watlow EZ-ZONE
®
RMC Module 82 Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[`S2;A]
[ SZ.A]
Output Digital (1 to 8)
Source Zone A
Set the instance of the
function selected above.
0 to 16 0 1042
[offset 30]
0x6A
(106)
1 to 8
0xC (12)
- - - - 6012 uint
RWES
[`o;Ct]
[ o.Ct]
Output Digital (1 to 8)
Control
Set the output control
type. This parameter
is only used with PID
control, but can be set
anytime.
[`Ftb] Fixed Time Base (34)
[`utb] Variable Time Base
(103)
Fixed
Time
Base
1022
[offset 30]
0x6A
(106)
1 to 8
2
- - - - 6002 uint
RWES
[`o;tb]
[ o.tb]
Output Digital (1 to 8)
Time Base
Set the time base for
fixed-time-base control.
0.1 to 60.0 seconds (solid-state
relay or switched dc)
5.0 to 60.0 seconds (mechani-
cal relay or NO-ARC power
control)
1.0 sec.
[SSR &
sw dc]
20.0 sec.
[mech,
relay,
NO-
ARC]
1024
[offset 30]
0x6A
(106)
1 to 8
3
- - - - 6003 float
RWES
[`o;Lo]
[ o.Lo]
Output Digital (1 to 8)
Low Power Scale
The power output will
never be less than the
value specified and will
represent the value at
which output scaling
begins.
0.0 to 100.0% 0.0% 1036
[offset 30]
0x6A
(106)
1 to 8
9
- - - - 6009 float
RWES
[`o;hi]
[ o.hi]
Output Digital (1 to 8)
High Power Scale
The power output will
never be greater than
the value specified and
will represent the value
at which output scaling
stops.
0.0 to 100.0% 100.0% 1038
[offset 30]
0x6A
(106)
1 to 8
0xA (10)
- - - - 6010 float
RWES
[`o;ty]
[ o.ty]
Output Process (1, 3, 5
or 7)
Type
Select whether the pro-
cess output will operate
in volts or milliamps.
[uoLt] Volts (104)
[`MA] Milliamps (112)
Volts 840 (1)
888 (3)
936 (5)
984 (7)
0x76 (118)
1 to 4
1
95 18001 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set
Vista de pagina 84
1 2 ... 80 81 82 83 84 85 86 87 88 89 90 ... 235 236

Comentarios a estos manuales

Sin comentarios