Watlow EZ-ZONE
®
RMC Module 86 Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[`A;hi]
[ A.hi]
Alarm (1 to 8)
High Set Point **
If Alarm Type (Setup
Page, Alarm Menu) is
set to:
process - set the pro-
cess value that will
trigger a high alarm.
deviation - set the
span of units from the
closed loop set point
that will trigger a low
alarm. A negative set
point represents a
value below closed loop
set point. A positive
set point represents a
value above closed loop
set point.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
300.0°F
or units
150.0°C
1740
[offset
60]
0x6D
(109)
1 to 8
1
19 9001 float
RWES
[`A;LA]
[ A.LA]
Alarm (1 to 8)
Latching
Turn alarm latching on
or off. A latched alarm
has to be turned off by
the user.
[nLAt] Non-Latching (60)
[`LAt] Latching (49)
Non-
Latching
1752
[offset 60]
0x6D
(109)
1 to 8
7
27 9007 uint
RWES
[`A;bL]
[ A.bL]
Alarm (1 to 8)
Blocking
Select when an alarm
will be blocked. After
startup and/or after the
set point changes, the
alarm will be blocked
until the process value
enters the normal range.
[`oFF] Off (62)
[`Str] Startup (88)
[StPt] Set Point (85)
[both] Both (13)
Off 1754
[offset 60]
0x6D
(109)
1 to 8
8
28 9008 uint
RWES
[`A;Si]
[ A.Si]
Alarm (1 to 8)
Silencing
Turn alarm silencing on
to allow the user to dis-
able this alarm.
[`oFF] Off (62)
[``on] On (63)
Off 1750
[offset 60]
0x6D
(109)
1 to 8
6
29 9006 uint
RWES
[A;dSP]
[A.dSP]
Alarm (1 to 8)
Display
Display an alarm mes-
sage when an alarm is
active.
[`oFF] Off (62)
[``on] On (63)
On 1770
[offset 60]
0x6D
(109)
1 to 8
0x10 (16)
30 9016 uint
RWES
[`A;dL]
[ A.dL]
Alarm (1 to 8)
Delay Time
Set the span of time
that the alarm will be
delayed after the process
value exceeds the alarm
set point.
0 to 9,999 seconds 0 1780
[offset 60]
0x6D
(109)
1 to 8
0x15 (21)
31 9021 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set