Watlow EZ-ZONE
®
RMC Module • 189 • Chapter 7 Features
Math
Sample and Hold
Range Low
Range High
Pressure Units
Altitude Units
Scale Low
Scale High
Function
Filter
Offset
Filter
If E = OFF, Output Value = Filter [A + Offset]
If E = ON, Output Value = Filter [last value
of A + Offset]
Display units follows Source A
Source Function A
Source Instance A
Source Zone A
Source Error A
Source Function B
Source Instance B
Source Zone B
Source Error B
Source Function C
Source Instance C
Source Zone C
Source Error C
Source Function D
Source Instance D
Source Zone D
Source Error D
Source Function E
Source Instance E
Source Zone E
Source Error E
Source Value A
Source Value B
Source Value C
Source Value D
Source Value E
Output Value
Error
Math
Dewpoint
Range Low
Range High
Pressure Units
Altitude Units
Scale Low
Scale High
Function
Filter
Offset
Filter
Output Value = Filter [427.26 * (CP *
B / 8.8618)
/ (17.27- (CP * B / 8.8618)) + 32 +
Offset]
Source A is used for Calculated
Pressure or CP ;
Note: For dewpoint, Source A is
temperature (F) and Source B is RH
(%). Saturation pressure calculation is
identical to that used in wet/dry
bulb. Result is in degrees F.
Source Function A
Source Instance A
Source Zone A
Source Error A
Source Function B
Source Instance B
Source Zone B
Source Error B
Source Function C
Source Instance C
Source Zone C
Source Error C
Source Function D
Source Instance D
Source Zone D
Source Error D
Source Function E
Source Instance E
Source Zone E
Source Error E
Source Value A
Source Value B
Source Value C
Source Value D
Source Value E
Output Value
Error
Output Function
This function configures and connects physical outputs to
internal functions.
Note:
Digital Outputs not included on these sheets
An error, when read, can indicate any of the following:
None, Open, Shorted, Measurement Error, Bad Cal Data,
Ambient Error, RTD Error, Fail, Math Error, Not Sourced,
Stale
Output
Overview
Instances - 0 to 8 per RMC
Output Value
Error
Output Low Power Scale
Output Time Base
Output Control
Output High Power Scale
Output Function
Output Function Instance
Output Source Zone
Output Source Error
[``o;u] Output Value : On, Off
[``Fn] Output Function : Off, Analog Input, Alarm, Cool Power, Heat
Power, Compare, Counter, Digital I/O. Profile Event Out A to H,
Function Key, Logic, Linearization, Math, Process Value, Special
Function Output 1 to 4, Timer, Variable, Limit
[`o;Ct] Output Control : Fixed Time Base, Variable Time Base
[``Fi] Output Function Instance : 1 to 250
[``Fi] Output Function Instance : 1 to 250
[`o;Lo] Output Low Power Scale : 0 to 100 %
[`o;hi] Output High Power Scale : 0 to 100 %
[`o;tb] Output Time Base : 0.1 to 60.0 seconds
[``S2] Output Source Zone : 0 to 16
[`S2;A] Source Zone A : 0 to 16
[otPt] Output Menu
[`SEt] Setup Page
[`o;ty] Output Type : Volts, Milliamps
[`S;Lo] Scale Low : 0.0 to 20.00
[`S;hi] Scale High : 0.0 to 20.00
[`r;Lo] Range Low : -1,999.000 to 9,999.000
[`r;hi] Range High : -1,999.000 to 9,999.000
[`o;CA] Calibration Offset : -1,999.000 to 9,999.000
[``o;u] Output Value : 0 to 10.0 volts or 0 to 20.00 milliamperes
[``Fn] Output Function : Off, Analog Input, Alarm, Cool Power, Heat
Power, Compare, Counter, Digital I/O. Profile Event Out A to H,
Function Key, Logic, Linearization, Math, Process Value, Special
Function Output 1 to 4, Timer, Variable