Warning: ç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices. Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life.
Note:
Maximum wire size termination and
torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12 AWG)
single-wire termination or two 1.31
mm
2
(16 AWG)
• 0.8 Nm (7.0 in-lb.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number.
Note:
To prevent damage to the controller,
do not connect wires to unused ter-
minals.
Note:
Maintain electrical isolation between
digital input-outputs, switched dc/open
collector outputs and process outputs
to prevent ground loops.
Note:
If the last two digits of the part number
are "12", this equipment is suitable for
use in CLASS I, DIVISION 2, Groups A,
B, C and D or Non-Hazardous locations
only. Temperature Code T4
Warning: ç
Explosion Hazard – Substitution of
component may impair suitability for
CLASS I, DIVISION 2.
Warning: ç
Explosion Hazard - Do not disconnect
while the circuit is live or unless the
area is known to be free of ignitable
concentrations of flammable sub-
stances.
Watlow EZ-ZONE
®
RMC Module 28 Chapter 2 Install and Wire
Output 1, 3, 5, 7 Mechanical Relay, Form C
RMC Part # Digit 5, 7, 9, 11 is H, J, K, L or M
normally open
normally closed
common
L_
K_
J_
Slot A, B, D, E
5 A at 240VÅ (ac) or
30VÎ (dc) maximum re-
sistive load
20 mA at 24V minimum
load
125 VA pilot duty at
120/240VÅ (ac), 25 VA at
24VÅ (ac)
100,000 cycles at rated
load
Output does not supply
power.
for use with ac or dc
See Quencharc note.
normally open
common
normally closed
L
_
K
_
J
_
Output 2, 4, 6, 8 Mechanical Relay, Form A
RMC Part # Digit 5, 7, 9, 11 is B, F, L or R
normally open
common
L_
K_
Slot A, B, D, E
5 A at 240VÅ (ac) or
30VÎ (dc) maximum re-
sistive load
20 mA at 24V minimum
inductive load
125 VA pilot duty at
120/240V Å(ac), 25 VA at
24V Å(ac)
100,000 cycles at rated
load
Output does not supply
power.
for use with ac or dc
See Quencharc note.
L
_
K
_