Watlow EZ-ZONE
®
RMC Module 176 Chapter 7 Features
Control Function
Control
Overview
Instances - 1 to 4 per RMC
Control Mode
Remote Set Point Enable
Remote Set Point Enable
Remote Set Point Type
User Failure Action
Loop Error Clear Request
Input Error Failure
Fixed Power
Open Loop Detect Enable
Open Loop Detect Time
Open Loop Detect Deviation
Ramp Action
Ramp Scale
Ramp Rate
Profiling Enable
Closed Loop Low Set Point
Set Point Open Limit Low
Closed Loop High Set Point
Set Point Open Limit High
Heat Algorithm
Cool Algorithm
TRU-TUNE+ Enable
Autotune Aggressiveness
Peltier Delay
TRU-TUNE+ Band
TRU-TUNE+ Gain
Cool Output Curve
Autotune Set Point
Autotune
Closed Loop Set Point
Idle Set Point
Heat Proportional Band
Cool Proportional Band
Heat Hysteresis
Cool Hysteresis
Deadband
Open Loop Set Point
Cool Power
Heat Power
Tune Status
Loop Error
Closed Loop Set Point
Open Loop Set Point
Loop Power
Process Value Active
Source Function A
Source Instance A
Source Zone A
Source Error A
Source Function B
Source Instance B
Source Zone B
Source Error B
Time Integral
Time Derivative
[SFn;A] Source Function A : Analog Input, Process Value
`[h;Ag] Heat Algorithm : Off, PID, On/Off
[`C;Ag] Cool Algorithm : Off, PID, On/Off
[t;tUn] TRU-TUNE+ Enable : No, Yes
[t;bnd] TRU-TUNE+ Band : 0 to 100
[`t;gn] TRU-TUNE+ Gain : 1 to 6
[t;Agr] Autotune Aggressiveness : Under, Critical, Over
[`r;En] Remote Set Point Enable : No, Yes
[`Si;b] Source Instance B (Remote Set Point Source Instance) : 1 to 250
[`S2;b] Source Zone B : 0 to 16
[MAn] Fixed Power : -100.0 to 100.0 %
[`L;dE] Open Loop Detect Enable : No, Yes
[`L;dt] Open Loop Detect Time : 0 to 3,600 seconds
[``rP] Ramp Action : Off, Startup, Set Point, Both
[`r;SC] Ramp Scale : Hours, Minutes
[`r;En] Remote Set Point Enable : No, Yes
[`C;M] Control Mode : Off, Auto, Manual
[A;tSP] Autotune Set Point : 50 to 200 %
[`AUt] Autotune : No, Yes
[`C;SP] Closed Loop Set Point : -1,999.000 to 9,999.000
[`id;S] Idle Set Point : -1,999.000 to 9,999.000
[`h;Pb] Heat Proportional Band : 0.001 to 9,999.000
[`h;hy] Heat Hysteresis : 0.001 to 9,999.000
[`C;Pb] Cool Proportional Band : 0.001 to 9,999.000
[`C;hy] Cool Hysteresis : 0.001 to 9,999.000
[``ti] Time Integral : 0 to 9,999 seconds
[``td] Time Derivative : 0 to 9,999 seconds
`[C;Cr] Cool Output Curve : Off, Non-linear curve 1, Non-linear curve 2
[`r;ty] Remote Set Point Type : Auto, Manual
[`L;SP] Low Set Point : -1,999.000 to 9,999.000
[`h;SP] High Set Point : -1,999.000 to 9,999.000
[SP;Lo] Set Point Open Limit Low : -100.0 to 100.0 %
[SP;hi] Set Point Open Limit High : -100.0 to 100.0 %
[`L;dd] Open Loop Detect Deviation : -1,999.000 to 9,999.000
[`r;rt] Ramp Rate : 0.000 to 9,999.000
[Pro;E] Profiling Enable: No, Yes
[``db] Deadband : -1,000.000 to 1,000.000
[`o;SP] Open Loop Set Point : -100.0 to 100.0 %
[`iS;A] Source Instance A : (not changeable)*
[LooP] Loop Menu
[`SEt] Setup Page
[LooP] Loop Menu
[oPEr] Operation Page
[`P;dL] Peltier Delay : 0.0 to 5.0
Note: Control Loop primary source instance must match
Process Value or Analog Input instance.
Loop Power : -100.0 to 100.0 %
Loop Error: None, Open Loop, Reversed Sensor
Loop Error Clear Request : Ignore, Clear
Tune Status : Off, Cross 1 Positive, Cross 1 Negative,
Cross 2 Positive, Cross 2 Negative, Cross 3 Positive,
Cross 3 Negative, Measuring Max, Measuring Min,
Calculating, Complete, Timeout
[C;MA] Control Mode Active : Off, Auto, Manual
[`h;Pr] Heat Power : 0.0 to 100.0 %
[`C;Pr] Cool Power : 0.0 to 100.0 %
[`C;SP] Closed Loop Set Point : -1,999.000 to 9,999.000
[`Pu;A] Process Value Active : -1,999.000 to 9,999.000
[Mon] Monitor Menu
[oPEr] Operation Page
Control Mode Active
[SFn;b] Source Function B : (Remote Set Point Source) : None, Analog
Input, Current, Cool Power, Heat Power, Power, Linearization,
Math, Process Value, Set Point Closed, Set Point Open, Variable
[fail] Input Error Failure : Off, Bumpless Transfer, Manual Power,
User
[`Ufa] User Failure Action : Off, Bumpless Transfer, Manual Power,
User