Watlow EZ-ZONE RMC Manual de usuario Pagina 118

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 236
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 117
Watlow EZ-ZONE
®
RMC Module 115 Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[gLbL]
[`Set]
Global Menu
[`C_F]
[ C_F]
Global
Display Units
Select which scale to use
for temperature.
[```F] °F (30)
[```C] °C (15)
°F 43348 0x67 (103)
1
5
- - - - 3005 - - - -
[AC;LF]
[AC.LF]
Global
AC Line Frequency
Set the frequency to the
applied ac line power
source.
[``50] 50 Hz (3)
[``60] 60 Hz (4)
60 Hz 1026 0x6A
(106)
1
4
- - - - 6004 uint
RWES
[sutb]
[Sutb]
Global
Synchronized Variable
Time Base
Used to acquire tighter
accuracy when running
a profile. A setting of
+0.01 would equate
to approximately +9
seconds/day (faster)
where a setting of -0.01
would equate to ap-
proximately -9 seconds/
day (slower).
-2.00 to 2.00 Percent 0.00 - - - - - - - - - - - - - - - - float
RWE
[d;prs]
[dPrS]
Global
Display Pairs
Defines the number of
Display Pairs.
1 to 10 1 - - - - 0x67 (103)
1
0x1C (28)
- - - - 3028 uint
RWES
[USr;S]
[USr.S]
Global
User Settings Save
Save all of this control-
ler's settings to the
selected set that have a
Data Type of RWES
[SEt1] User Set 1 (101)
[SEt2] User Set 2 (102)*
[none] None (61)
* Starting with firmware re-
lease 6, there is only one user
set.
None
26
0x65
(101)
1
0x0E (14)
118 1014 uint
RWE
[USr;r]
[USr.r]
Global
User Settings Restore
Replace all of this con-
troller's settings with
another set.
[FCty] Factory (31)
[none] None (61)
[SEt1] User Set 1 (101)
[SEt2] User Set 2 (102)*
* Starting with firmware re-
lease 6, there is only one user
set.
None
24
0x65
(101)
1
0xD (13)
117 1013 uint
RWE
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set
Vista de pagina 117