Watlow EZ-ZONE
®
RMC Module • 73 • Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[SFn;A]
[SFn.A]
Action (1 to 8)
Source Function A
Set the event or func-
tion that will trigger the
action.
[[nonE] None (61)
[ALM] Alarm (6)
[`CPE] Compare (230)
[`Ctr] Counter (231)
[`dio] Digital I/O (1142)
[Ent;A] Profile Event Out A
(233)
[Ent;b] Profile Event Out B
(234)
[Ent;C] Profile Event Out C
(235)
[Ent;d] Profile Event Out D
(236)
[Ent;E] Profile Event Out E
(247)
[Ent;F] Profile Event Out F
(248)
[Ent;g] Profile Event Out G
(249)
[Ent;h] Profile Event Out H
(250)
[`FUn] Function Key (1001)
[lim] Limit (126)
[`lgC] Logic (239)
[tMr] Timer (244)
[`uAr] Variable (245)
None 1590
[offset 20]
0x6E
(110)
1 to 8
6
- - - - 10006 uint
RWES
[`Si;A]
[ Si.A]
Action (1 to 8)
Source Instance A
Set the instance of the
function selected above.
1 to 250 1 1582
[offset 20]
0x6E
(110)
1 to 8
2
- - - - 10002 uint
RWES
[`S2;A]
[ SZ.A]
Action (1 to 8)
Source Zone A
Set the zone of the func-
tion selected above.
0 to 16 0 1592
[offset 20]
0x6E
(110)
1 to 8
7
- - - - 10007 uint
RWES
[`LEu]
[ LEv]
Action (1 to 8)
Active Level
Set the action that will
be considered a true
state.
[LoW] Low (53)
[high] High (37)
High 1580
[offset 20]
0x6E
(110)
1 to 8
1
137 10001 uint
RWES
[Lim]
[`Set]
Limit Menu
[`L;Sd]
[ L.Sd]
Limit (1 to 4)
Sides
Select which side or
sides of the process val-
ue will be monitored.
[both] Both (13)
[high] High (37)
[LoW] Low (53)
Both 728
[offset 30]
0x70 (112)
1 to 4
5
40 12005 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set