Watlow EZ-ZONE
®
RMC Module • 78 • Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[`r;ty]
[ r.ty]
Control Loop (1 to 4)
Remote Set Point Type
Set what type of set
point will be used.
[AUto] Auto (10)
[MAn] Manual (54)
Auto 2542
[offset 80]
0x6B
(107)
1 to 4
0x16 (22)
- - - - 7022 uint
RWES
[`UFA]
[UFA]
Control Loop (1 to 4)
User Failure Action
Select what the control-
ler outputs will do when
the user switches control
to manual mode.
[`oFF] Off, sets output power to
0% (62)
[bPLS] Bumpless transfer, main-
tains same output power, if it
was less than 75% and stable,
otherwise 0% (14)
[MAn] Manual Power, sets
output power to Fixed Power
setting (54)
[USEr] User, sets output power
to last open-loop set point the
user entered (100)
User 2522
[offset 80]
0x6B
(107)
1 to 4
0xC (12)
- - - - 7012 uint
RWES
[FAiL]
[FAiL]
Control Loop (1 to 4)
Input Error Failure
Select what the control-
ler outputs will do when
an input error switches
control to manual mode.
[`oFF] Off, sets output power to
0% (62)
[bPLS] Bumpless transfer, main-
tains same output power, if it
was less than 75% and stable,
otherwise 0% (14)
[MAn] Manual Power, sets
output power to Fixed Power
setting (54)
[USEr] User, sets output power
to last open-loop set point the
user entered (100)
User 2524
[offset 80]
0x6B
(107)
1 to 4
0xD (13)
- - - - 7013 uint
RWES
[MAn]
[MAn]
Control Loop (1 to 4)
Fixed Power
Set the manual output
power level that will
take effect if an input er-
ror failure occurs while
User Failure Action is
set to Manual Power.
Set Point Open Loop Limit Low
to Set Point Open Loop Limit
High (Setup Page)
0.0 2520
[offset 80]
0x6B
(107)
1 to 4
0xB (11)
- - - - 7011 float
RWES
[`L;dE]
[ L.dE]
Control Loop (1 to 4)
Open Loop Detect En-
able
Turn on the open-loop
detect feature to monitor
a closed-loop operation
for the appropriate re-
sponse.
[``no] No (59)
[`YES} Yes (106)
No 2262
[offset 70]
0x97 (151)
1 to 4
0x16 (22)
74 8039 uint
RWES
[`L;dt]
[ L.dt]
Control Loop (1 to 4)
Open Loop Detect
Time
The Open Loop Detect
Deviation value must oc-
cur for this time period
to trigger an open-loop
error.
0 to 3,600 seconds 240 2264
[offset 70]
0x97 (151)
1 to 4
0x17 (23)
75 8040 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set