Vista de pagina 78
Watlow EZ-ZONE
®
RML Module 76 Chapter 5 Factory Page
RM Limit Module Factory Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[diAg]
[FCty]
Diagnostics Menu
[``Pn]
[ Pn]
Diagnostics Menu
Part Number
Display this controller's part
number.
24 - - - - 0x65
(101)
1
9
66 1009 uint
RWE
No Dis-
play
Diagnostics Menu
Device Name
Read the hardware ID.
0 to 2,147,483,647 - - - - - - - - 0x65
(101)
1
0x0B (11)
- - - - 1011 float
RWE
No Dis-
play
Diagnostics Menu
Device Status
Read the hardware ID.
0 to 2,147,483,647 - - - - 30 0x65
(101)
1
0x10 (16)
- - - - 1016 float
RWE
[`rEu]
[ rEu]
Diagnostics Menu
Software Revision
Display this controller's firm-
ware revision number.
5 - - - - 4 0x65
(101)
1 to 5
0x11 (17)
67 1017 uint
R
[S;bLd]
[S.bLd]
Diagnostics Menu
Software Build Number
Display the firmware build
number.
0 to 2,147,483,647 - - - - 8 0x65
(101)
1 to 5
5
- - - - 1005 float
R
[``Sn]
[ Sn]
Diagnostics Menu
Serial Number
Display the serial number.
0 to 2,147,483,647 - - - - 12 0x65
(101)
1
7
- - - - 1032 float
RWE
[dAtE]
[dAtE]
Diagnostics Menu
Date of Manufacture
Display the date code. Date
code format is YYWW, where
YY is last two digits of the
year, and WW is the week of
the year.
0 to 2,147,483,647 - - - - 14 0x65
(101)
1
8
- - - - 1008 float
RWE
No Dis-
play
Diagnostics Menu
Hardware ID
Read the hardware ID.
0 to 2,147,483,647 - - - - 0 0x65
(101)
1
1
- - - - 1001 float
RWE
[`CAL]
[FCty]
Calibration Menu
[`Mu]
[ Mv]
Calibration Menu (1 to 12)
Electrical Measurement
Read the raw electrical value
for this input in the units cor-
responding to the Sensor Type
(Setup Page, Analog Input
Menu) setting.
-3.4e38 to 3.4e38 450
[offset
90]
0x68
(104)
1 to 0x0C
(12)
0x15 (21)
- - - - 4021 float
R
[ELi;o]
[ELi.o]
Calibration Menu (1 to 12)
Electrical Input Offset
Change this value to calibrate
the low end of the input range.
-1,999.000 to 9,999.000 0.0 428
[offset
90]
0x68
(104)
1 to 0x0C
(12)
0xA (10)
- - - - 4010 float
RWES
Note: Some values will be rounded off to fit in the four-character display. Full values can
be read with another interface.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EE-
PROM
S: User
Set
Vista de pagina 78
1 2 ... 74 75 76 77 78 79 80 81 82 83 84 ... 126 127