Watlow EZ-ZONE RM Limit Module Rev C Manual de usuario Pagina 66

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 127
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 65
Watlow EZ-ZONE
®
RML Module 63 Chapter 4 Setup Page
RM Limit Module Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[SFn;E]
[SFn.E]
Logic (1 to 16)
Source Function E
Set the type of function
that will be used for this
source.
[[nonE] None (61)
[ALM] Alarm Reset (6)
[`CPE] Compare (230)
[`Ctr] Counter (231)
[`dio] Digital I/O (1142)
[Ent;A] Profile Event Out A
(233)
[Ent;b] Profile Event Out B
(234)
[Ent;C] Profile Event Out C
(235)
[Ent;d] Profile Event Out D
(236)
[Ent;E] Profile Event Out E
(247)
[Ent;F] Profile Event Out F
(248)
[Ent;g] Profile Event Out G
(249)
[Ent;h] Profile Event Out H
(250)
[`FUn] Function Key (1001)
[lim] Limit (126)
[`lgC] Logic (239)
[SoF;1] Special Function Out-
put 1 (1532)
[SoF;2] Special Function Out-
put 2 (1533)
[SoF;3] Special Function Out-
put 3 (1534)
[SoF;4] Special Function Out-
put 4 (1535)
[tMr] Timer (244)
[`uAr] Variable (245))
None 4638
[offset 80]
0x7F (127)
1 to 16
5
- - - - 27005 uint
RWES
[`Si;E]
[ Si.E]
Logic (1 to 16)
Source Instance E
Set the instance of the
function selected above.
1 to 250 1 4654
[offset 80]
0x7F (127)
1 to 16
D (13)
- - - - 27013 uint
RWES
[`s2;E]
[ SZ.E]
Logic (1 to 16)
Source Zone E
Set the zone of the function
selected above.
0 to 16 0 4670
[offset 80]
0x7F (127)
1 to 16
0x15 (21)
- - - - 27021 uint
RWES
Note: Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User
Set
Vista de pagina 65
1 2 ... 61 62 63 64 65 66 67 68 69 70 71 ... 126 127

Comentarios a estos manuales