Watlow EZ-ZONE RM Limit Module Rev C Manual de usuario Pagina 75

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 127
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 74
Watlow EZ-ZONE
®
RML Module 72 Chapter 4 Setup Page
RM Limit Module Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[M;hL]
[M.hL]
Communications
Modbus Word Order
Select the word order of
the two 16-bit words in the
floating-point values.
[hiLo] Word High Low
(1330)
[Lohi] Word Low High
(1331)
Low High 3498 0x96 (150)
1
5
- - - - 17043 uint
RWE
[`C_F]
[ C_F]
Communications
Comm Units
Select which scale to use for
temperature over comms.
°F (30)
°C (15)
°F 3500 0x96 (150)
1
6
- - - - 17050 uint
RWE
[`nU;S]
[ nV.S]
Communications (1)
Non-volatile Save
If set to Yes all values writ-
ten to the control will be
saved in EEPROM.
Note:
Any value that is changed
from the RUI or over a
communications port will
initiate a write to the EE-
PROM. Life of EEPROM
is approximately one mil-
lion writes.
[`yes] Yes (106)
[``no] No (59)
Yes 3504 0x96 (150)
1
8
198 17051 uint
RWE
Note: Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User
Set
Vista de pagina 74
1 2 ... 70 71 72 73 74 75 76 77 78 79 80 ... 126 127

Comentarios a estos manuales

Sin comentarios