Watlow EZ-ZONE
®
RML Module • 67 • Chapter 4 Setup Page
RM Limit Module • Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[MAt]
[`Set]
Math Menu
[``Fn]
[ Fn]
Math (1 to 16)
Function
Set the operator that will
be applied to the sources.
[`oFF] Off (62)
[`Aug] Average (1367)
[`P;SC] Process Scale (1371)
[`d;SC] Deviation Scale
(1372)
[``s;o] Switch Over (1370)
[diFF] Differential (1373)
[rAti] Ratio (1374)
[`Add] Add (1375)
[MUL] Multiply (1376)
[A;diF] Absolute Difference
(1377)
[Min] Minimum (1378)
[MAH] Maximum (1379)
[root] Square Root (1380)
[hoLd] Sample and Hold
(1381)
[`alt] Altitude (1349)
[dew] Dewpoint (1650)
Off 3550
[offset 70]
0x7D
(125)
1 to 16
0x15 (21)
128 25021 uint
RWES
[SFn;A]
[SFn.A]
Math (1 to 16)
Source Function A
Set the type of function
that will be used for this
source.
[nonE] None (61)
[``Ai] Analog Input (142)
[CUrr] Current (22)
[`C;Pr] Cool Power, Control
Loop (161)
[`h;Pr] Heat Power, Control
Loop (160)
[PWr] Power, Control Loop
(73)
[`Lnr] Linearization (238)
[MAt] Math (240)
[``Pu] Process Value (241)
[`SP;C] Set Point Closed,
Control Loop (242)
[`SP;o] Set Point Open, Con-
trol Loop (243)
[`uAr] Variable (245)
None 3510
[offset 70]
0x7D
(125)
1 to 16
1
- - - - 25001 uint
RWES
[`Si;A]
[ Si.A]
Math (1 to 16)
Source Instance A
Set the instance of the
function selected above.
1 to 250 1 3520
[offset 70]
0x7D
(125)
1 to 16
6
- - - - 25006 uint
RWES
[`S2;A]
[ SZ.A]
Math (1 to 16)
Source Zone A
Set the zone of the function
selected above.
0 to 16 0 3530
[offset 70]
0x7D
(125)
1 to 16
0xB (11)
- - - - 25011 uint
RWES
Note: Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User
Set