Watlow EZ-ZONE
®
RML Module • 47 • Chapter 4 Setup Page
RM Limit Module • Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`Si;A]
[ Si.A]
Action (1 to 16)
Source Instance A
Set the instance of the
function selected above.
1 to 250 1 2212
[offset 20]
0x6E
(110)
1 to 16
2
- - - - 10002 uint
RWES
[`S2;A]
[ SZ.A]
Action (1 to 16)
Source Zone A
Set the zone of the function
selected above.
0 to 16 0 2222
[offset 20]
0x6E
(110)
1 to 16
7
- - - - 10007 uint
RWES
[`LEu]
[ LEv]
Action (1 to 16)
Active Level
Set the action that will be
considered a true state.
[LoW] Low (53)
[high] High (37)
High 2230
[offset 20]
0x6E
(110)
1 to 16
1
137 10001 uint
RWES
[Lim]
[`Set]
Limit Menu
[`L;Sd]
[ L.Sd]
Limit (1 to 12)
Sides
Select which side or sides
of the process value will be
monitored.
[both] Both (13)
[high] High (37)
[LoW] Low (53)
Both 1498
[offset 30]
0x70 (112)
1 to 12
5
40 12005 uint
RWES
[`L;hy]
[ L.hy]
Limit (1 to 12)
Hysteresis
Set the hysteresis for the
limit function. This deter-
mines how far into the safe
range the process value
must move before the limit
can be cleared.
0.001 to 9,999.000°F or units
0.001 to 5,555.000°C
3.0°F or
units
2.0°C
1492
[offset 30]
0x70 (112)
1 to 12
2
41 12002 float
RWES
[SP;Lh]
[SP.Lh]
Limit (1 to 12)
Set Point Limit High
Set the high end of the
limit set point range.
-1,999.000 to 9,999.000 9,999.000 1506
[offset 30]
0x70 (112)
1 to 12
9
39 12009 float
RWES
[SP;Ll]
[SP.LL]
Limit (1 to 12)
Set Point Limit Low
Set the low end of the limit
set point range.
-1,999.000 to 9,999.000 -1,999.000 1508
[offset 30]
0x70 (112)
1 to 12
0xA (10)
38 12010 float
RWES
[`Lh;S]
[ Lh.S]
Limit (1 to 12)
High Set Point
Set the high process value
that will trigger the limit.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
1496
[offset 30]
0x70 (112)
1 to 12
4
42 12004 float
RWES
[`LL;S]
[ LL.S]
Limit (1 to 12)
Low Set Point
Set the low process value
that will trigger the limit.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
1494
[offset 30]
0x70 (112)
1 to 12
3
43 12003 float
RWES
[SFn;A]
[SFn.A]
Limit (1 to 12)
Source Function A
Set the source for the limit
reset function.
[nonE] None (61)
[`dio] Digital I/O (1142)
[`FUn] Function Key (1001)
[`uAr] Variable (245)
None - - - - 0x70 (112)
1 to 12
0x0F (15)
- - - - 12015 uint
RWES
[`Si;A]
[ Si.A]
Limit (1 to 12)
Source Instance A
Set the instance of the
function selected above.
1 or 250 1 - - - - 0x70 (112)
1 to 12
0x10 (16)
- - - - 12016 uint
RWES
Note: Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User
Set