Watlow EZ-ZONE RM Limit Module Rev C Manual de usuario Pagina 30

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 127
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 29
Watlow EZ-ZONE
®
RML Module 27 Chapter 2 Install and Wire
98
99
CF
CD
CE
B5
D6
D5
- A
+ B
common
Power
Supply
- A
+ B
common
RUI/Gateway
EZKB-_A_ _-_ _ _ _
EZ-ZONE
®
PM
fuse
EZ-ZONE
®
RML
RMLx-xxxx-xAxx
Limit Module
Slot C
- A
+ B
common
CY
CX
CZ
CE
CD
CF
99
98
98
99
CF
CD
CE
98
99
CC
CA
CB
B5
D6
D5
- A
+ B
common
Power
Supply
- A
+ B
common
PLC
EZ-ZONE
®
PM
fuse
Slot C
- A
+ B
common
CY
CX
CZ
CB
CA
CC
99
98
EZ-ZONE
®
RML
RMLx-xxxx-x1xx
Limit Module
- A
+ B
common
Wiring a Serial EIA-485 Network
Do not route network wires with power wires. Con-
nect network wires in daisy-chain fashion when con-
necting multiple devices in a network.
A termination resistor is required. Place a 120 Ω
resistor across T+/R+ and T-/R- of the last controller
on a network.
Only one protocol per port is available at a time:
either Modbus RTU or Standard Bus.
A network using Watlow's Standard Bus and an RUI/Gate
way.
A network using Modbus RTU
Vista de pagina 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 126 127

Comentarios a estos manuales

Sin comentarios