Watlow EZ-ZONE
®
RMS Module • 78 • Chapter 4 Setup Page
RM Scanner Module • Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`Si;E]
[ Si.E]
Math (1 to 24)
Source Instance E
Set the instance of the
function selected above.
1 to 250 1 3518
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0xA (10)
- - - - 25010 uint
RWES
[`s2;E]
[ SZ.E]
Math (1 to 24)
Source Zone E
Set the zone of the function
selected above.
0 to 16 0 3528
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0xF (15)
- - - - 25015 uint
RWES
[`S;Lo]
[ S.Lo]
Math (1 to 24)
Scale Low
Active for Process or Devia-
tion Scale of Source A only.
-1,999.000 to 9,999.000 °F
or units
-1,128.333 to 5537.223 °C
0.0 3546
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0x18 (24)
70 25024 float
RWES
[`S;hi]
[ S.hi]
Math (1 to 24)
Scale High
Active for Process or Devia-
tion Scale of Source A only
-1,999.000 to 9,999.000 °F
or units
-1,128.333 to 5537.223 °C
1.0 3548
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0x19 (25)
71 25025 float
RWES
[Unit]
[Unit]
Math (1 to 24)
Units
Set units for Source.
[`Src] Source (1539)
[nonE] None (61)
[`A;tP] Absolute Temperature
(1540)
[`r;tp] Relative Tempera-
ture (1541)
[PWr] Power (73)
[`pro] Process (75)
[``rh] Relative Humidity
(1538)
Source 3562
[offset 70]
0x7D
(125)
1 to 24
0x20 (32)
- - - - 25032 uint
RWES
[`r;Lo]
[ r.Lo]
Math (1 to 24)
Range Low
Active for Process or Devia-
tion Scale of Source A only.
-1,999.000 to 9,999.000 °F
or units
-1,128.333 to 5537.223 °C
0.0 3550
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0x1A (26)
72 25026 float
RWES
[`r;hi]
[ r.hi]
Math (1 to 24)
Range High
Active for Process or Devia-
tion Scale of Source A only
-1,999.000 to 9,999.000 °F
or units
-1,128.333 to 5537.223 °C
1.0 3552
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0x1B (27)
73 25027 float
RWES
[p;unt]
[P.unt]
Math (1 to 24)
Pressure Units
Select units of Source A
when function is Pressure
to Altitude conversion only
[`psi] Pounds per square
inch (1671)
[mbr] mbar (1672)
[torr] Torr (1673)
[pasc] Pascal (1674)
[atm] Atmosphere (1675)
Pressure
Units
3558
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0x1E (30)
- - - - 25030 uint
RWES
[a;unt]
[A.unt]
Math (1 to 24)
Altitude Units
Select units of output value
when function is Pressure
to Altitude conversion only.
[``ft] Feet (1674)
[`Hft] Kilofeet (1671)
Kilofeet 3560
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0x1F (31)
- - - - 25031 uint
RWES
Note: Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User
Set
Comentarios a estos manuales