Vista de pagina 65
Watlow EZ-ZONE
®
RMS Module 63 Chapter 4 Setup Page
RM Scanner Module Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[SFn;A]
[SFn.A]
Timer (1 to 24)
Source Function A
Set the type of function
that will be used for this
source (run signal).
[nonE] None (61)
[ALM] Alarm Reset (6)
[`CPE] Compare (230)
[`Ctr] Counter (231)
[`dio] Digital I/O (1142)
[Ent;A] Profile Event Out A
(233)
[Ent;b] Profile Event Out B
(234)
[Ent;C] Profile Event Out C
(235)
[Ent;d] Profile Event Out D
(236)
[Ent;E] Profile Event Out E
(247)
[Ent;F] Profile Event Out F
(248)
[Ent;g] Profile Event Out G
(249)
[Ent;h] Profile Event Out H
(250)
[`FUn] Function Key (1001)
[`lgC] Logic (239)
[SoF;1] Special Function Out-
put 1 (1532)
[SoF;2] Special Function Out-
put 2 (1533)
[SoF;3] Special Function Out-
put 3 (1534)
[SoF;4] Special Function Out-
put 4 (1535)
[tMr] Timer (244)
[`uAr] Variable (245)
None 10140
[offset 50]
0x83 (131)
1 to 0x18
(24)
1
- - - - 31001 uint
RWES
[`Si;A]
[ Si.A]
Timer (1 to 4)
Source Instance A
Set the instance of the
function selected above.
1 to 250 1 10144
[offset 50]
0x83 (131)
1 to 0x18
(24)
3
- - - - 31003 uint
RWES
[`S2;A]
[ SZ.A]
Timer (1 to 4)
Source Zone A
Set the zone of the function
selected above.
0 to 16 0 10148
[offset 50]
0x83 (131)
1 to 0x18
(24)
5
- - - - 31005 uint
RWES
[sas;A]
[SAS.A]
Timer (1 to 4)
Source Active State A
Set what state will be read
as on.
[high] High (37)
[LoW] Low (53)
High 10160
[offset 50]
0x83 (131)
1 to 0x18
(24)
0xB (11)
- - - - 31011 uint
RWES
Note: Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User
Set