Watlow EZ-ZONE
®
RMS Module 38 Chapter 3 Operations Page
RM Scanner Module Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
No Dis-
play
Alarm (1 to 16)
Silenced
Read this register to de-
termine if the alarm is
silenced
No (59)
Yes (106)
None 2520
[offset 60]
0x6D
(109)
1 to 0x10
(16)
0x0B (11)
- - - - 9011
uint
R
No Dis-
play
Alarm (1 to 16)
Clearable
Read to determine if an
alarm can be cleared
No (59)
Yes (106)
None 2522
[offset 60]
0x6D
(109)
1 to 0x10
(16)
0xC (12)
- - - - 9012 uint
R
No Dis-
play
Alarm (1 to 16)
Clear Request
Write to this register to
clear an alarm
Clear (0)
No Change (255)
None 2524
[offset 60]
0x6D
(109)
1 to 0x10
(16)
0xD (13)
32 9013
uint
RW
No Dis-
play
Alarm (1 to 16)
Silence Request
Write to this register to
silence an alarm
Clear (0)
No Change (255)
None 2526
[offset 60]
0x6D
(109)
1 to 0x10
(16)
0x0E (14)
33 9014
uint
RW
No Dis-
play
Alarm (1 to 16)
Alarm Working Process
Value
Read process value used
by alarms
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
None 2536
[offset 60]
0x6D
(109)
1 to 0x10
(16)
0x13 (19)
- - - - 9019
float
R
No Dis-
play
Alarm (1 to 16)
Alarm Working Set
Point
Read set point used by
alarms
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
None 2538
[offset 60]
0x6D
(109)
1 to 0x10
(16)
0x14 (20)
- - - - 9020
float
R
No Dis-
play
Alarm (1 to 16)
Output Value
Read state of alarm out-
put
On (63)
Off (62)
None 2546
[offset 60]
0x6D
(109)
1 to 0x10
(16)
0x18 (24)
- - - - 9024
uint
R
[`Lnr]
[oPEr]
Linearization Menu
[`Su;A]
[ Su.A]
Linearization (1 to 24)
Source Value A
View the value of Source
A.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
11346
[offset 70]
0x86
(134)
1 to 0x18
(24)
4
- - - - 34004 float
R
[oFSt]
[oFSt]
Linearization (1 to 24)
Offset
Set an offset to be applied
to this function's output.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0 11350
[offset 70]
0x86
(134)
1 to 0x18
(24)
6
- - - - 34006 float
RWES
[``o;u]
[ o.v]
Linearization (1 to 24)
Output Value
View the value of this
function's output.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
11352
[offset 70]
0x86
(134)
1 to 0x18
(24)
7
- - - - 34007 float
R
Note: Some values will be rounded off to fit in the four-character display. Full values
can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User Set