Watlow EZ-ZONE
®
RMS Module • 41 • Chapter 3 Operations Page
RM Scanner Module • Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
No Dis-
play
Counter (1 to 24)
Error
Read reported cause for
counter error
None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
9210
[offset 40]
0x82
(130)
1 to 0x18
(24)
0x10 (16)
- - - - 30016 uint
R
[`LgC]
[oPEr]
Logic Menu
[`Su;A]
[ Su.A]
Logic (1 to 24)
Source Value A
View the value of Source
A.
[`off] Off (62)
[``on] On (63)
6348
[offset 80]
0x7F
(127)
1 to 0x18
(24)
0x19 (25)
- - - - 27025 uint
R
[`Su;b]
[ Su.b]
Logic (1 to 24)
Source Value B
View the value of Source
B.
[`off] Off (62)
[``on] On (63)
6350
[offset 80]
0x7F
(127)
1 to 0x18
(24)
0x1A (26)
- - - - 27026 uint
R
[`Su;C]
[ Su.C]
Logic (1 to 24)
Source Value C
View the value of Source
C.
[`off] Off (62)
[``on] On (63)
6352
[offset 80]
0x7F
(127)
1 to 0x18
(24)
0x1B (27)
- - - - 27027 uint
R
[`Su;d]
[ Su.d]
Logic (1 to 24)
Source Value D
View the value of Source
D.
[`off] Off (62)
[``on] On (63)
6354
[offset 80]
0x7F
(127)
1 to 0x18
(24)
0x1C (28)
- - - - 27028 uint
R
[`Su;E]
[ Su.E]
Logic (1 to 24)
Source Value E
View the value of Source
E.
[`off] Off (62)
[``on] On (63)
6356
[offset 80]
0x7F
(127)
1 to 0x18
(24)
0x1D (29)
- - - - 27029 uint
R
[`Su;F]
[ Su.F]
Logic (1 to 24)
Source Value F
View the value of Source
F.
[`off] Off (62)
[``on] On (63)
6358
[offset 80]
0x7F
(127)
1 to 0x18
(24)
0x1E (30)
- - - - 27030 uint
R
[`Su;g]
[ Su.g]
Logic (1 to 24)
Value Source G
View the value of Source
G.
[`off] Off (62)
[``on] On (63)
6360
[offset 80]
0x7F
(127)
1 to 0x18
(24)
0x1F (31)
- - - - 27031 uint
R
[`Su;h]
[ Su.h]
Logic (1 to 24)
Source Value H
View the value of Source
H.
[`off] Off (62)
[``on] On (63)
6362
[offset 80]
0x7F
(127)
1 to 0x18
(24)
0x20 (32)
- - - - 27032 uint
R
Note: Some values will be rounded off to fit in the four-character display. Full values
can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User Set
Comentarios a estos manuales