Watlow EZ-ZONE
®
RMS Module 36 Chapter 3 Operations Page
RM Scanner Module Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[`Su;c]
[ Sv.c]
Process Value (1 to 16)
Source Value C
View the value of Source C.
-1,999.000 to 9,999.000°F
or units
-1,110.556 to 5,555.000°C
- - - - 5214
[offset 70]
0x7E (126)
1 to 0x10
(16)
0x12 (18)
- - - - 26018 float
R
[`Su;d]
[ Sv.d]
Process Value (1 to 16)
Source Value D
View the value of Source D.
-1,999.000 to 9,999.000°F
or units
-1,110.556 to 5,555.000°C
- - - - 5216
[offset 70]
0x7E (126)
1 to 0x10
(16)
0x13 (19)
- - - - 26019 float
R
[`Su;E]
[ Sv.E]
Process Value (1 to 16)
Source Value E
View the value of Source E.
-1,999.000 to 9,999.000°F
or units
-1,110.556 to 5,555.000°C
- - - - 5218
[offset 70]
0x7E (126)
1 to 0x10
(16)
0x14 (20)
- - - - 26020 float
R
[oFSt]
[oFSt]
Process Value (1 to 16)
Offset
Set an offset to be applied
to this function's output.
-1,999.000 to 9,999.000°F
or units
-1,110.556 to 5,555.000°C
0 5224
[offset 70]
0x7E (126)
1 to 0x10
(16)
0x17 (23)
- - - - 26023 float
RWES
[``o;u]
[ o.v]
Process Value (1 to 16)
Output Value
View the value of this func-
tion block's output.
-1,999.000 to 9,999.000°F
or units
-1,110.556 to 5,555.000°C
0.0 5222
[offset 70]
0x7E (126)
1 to 0x10
(16)
0x16 (22)
- - - - 26022 float
R
No Dis-
play
Process Value (1 to 16)
Error
View reported cause for
Linearization output mal-
function.
None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad calibration data (139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
None 5232
[offset 70]
0x7E
(126)
1 to 0x10
(16)
0x1B (27)
- - - - 26027 uint
R
[`dio]
[oPEr]
Digital Input/Output Menu
[`do;S]
[ do.S]
Digital Output (1 to 12)
Output State
View the state of this out-
put.
[`off] Off (62)
[``on] On (63)
1832
[offset 30]
0x6A (106)
1 to 0x0c
(12)
7
46 6007 uint
R
[`di;S]
[ di.S]
Digital Input (1 to 12)
Input State
View this event input state.
[`off] Off (62)
[``on] On (63)
1840
[offset 30]
0x6A (106)
1 to 0x0c
(12)
0xB (11)
- - - - 6011 uint
R
No Dis-
play
Digital Input (1 to 12)
Error
View reported cause for
digital input/output mal-
function.
None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad calibration data (139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
None 1848
[offset 30]
0x6A
(106)
1 to 0x0c
(12)
15
- - - - 6015 uint
R
Note: Some values will be rounded off to fit in the four-character display. Full values
can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM