Watlow EZ-ZONE RM-Scanner-Modul Manual de usuario Pagina 43

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 140
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 42
Watlow EZ-ZONE
®
RMS Module 40 Chapter 3 Operations Page
RM Scanner Module Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[``E;t]
[ E.t]
Timer (1 to 24)
Elapsed Time
View the value of this
function's elapsed time.
0 to 30,000.0 seconds 0 10170
[offset 50]
0x83
(131)
1 to 0x18
(24)
0x10 (16)
- - - - 31016 float
R
[``o;u]
[ o.v]
Timer (1 to 24)
Output Value
View the value of this
function's output.
[`off] Off (62)
[``on] On (63)
- - - - 10158
[offset 50]
0x83
(131)
1 to 0x18
(24)
0x11 (17)
- - - - 31010 uint
R
No Dis-
play
Timer (1 to 24)
Running
Read to determine if timer
is running
Off (62)
On (63)
- - - - 10168
[offset 50]
0x83
(131)
1 to 0x18
(24)
0x0F (15)
- - - - 31015 uint
R
No Dis-
play
Timer (1 to 24)
Error
Read reported cause for
timer error
None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
10174
[offset 50]
0x83
(131)
1 to 0x18
(24)
0x12 (18)
- - - - 31018 uint
R
[`Ctr]
[oPEr]
Counter Menu
[`Cnt]
[ Cnt]
Counter (1 to 24)
Count
View the function's total
count.
0 to 9,999 9208
[offset 40]
0x82
(130)
1 to 0x18
(24)
0xF (15)
125 30015 uint
R
[`Su;A]
[ Su.A]
Counter (1 to 24)
Source Value A
View the value of Source
A.
[`off] Off (62)
[``on] On (63)
9192
[offset 40]
0x82
(130)
1 to 0x18
(24)
7
- - - - 30007 uint
R
[`Su;b]
[ Su.b]
Counter (1 to 24)
Source Value B
View the value of Source
B.
[`off] Off (62)
[``on] On (63)
9194
[offset 40]
0x82
(130)
1 to 0x18
(24)
8
- - - - 30008 uint
R
[``o;u]
[ o.v]
Counter (1 to 24)
Output Value
View the value of this
function's output.
[`off] Off (62)
[``on] On (63)
9198
[offset 40]
0x82
(130)
1 to 0x18
(24)
0xA (10)
- - - - 30010 uint
R
Note: Some values will be rounded off to fit in the four-character display. Full values
can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User Set
Vista de pagina 42
1 2 ... 38 39 40 41 42 43 44 45 46 47 48 ... 139 140

Comentarios a estos manuales

Sin comentarios