RMS Module • 118 • Chapter 6 Features
Counter Function
Function counts up or down from Load Value and produces
Output Value = On when Count = Target Value.
Note:
Count value clears on power loss.
Load Value restored on power up.
[SFn;A] Source Function A (Clock) : None, Alarm, Compare, Counter, Digital I/O,
Profile Event Out A to H, Function Key, Logic, Timer, Variable
[SFn;b] Source Function B (Load) :
Profile Event Out A to H, Function Key, Logic, Timer, Variable
None, Alarm, Compare, Counter, Digital I/O,
[S2;A] Source A : 0 to 16Zone
[S2;b] Source B : 0 to 16Zone
[Si;A] Source A : 1 to 250Instance
[Si;b] Source B : 1 to 250Instance
[Su;A] Source A : Off, OnValue
[Su;b] Source Value B : Off, On
[o;u] Output Value : Off, On
[trgt] Target Value : 0 to 9,999
[LAt] Latching : No, Yes
[Cnt] Count : 0 to 9,999
[SAS;b] Source Active State B (Active State Load) : High, Low
[LoAd] Load Value : 0 to 9,999
[Fn] Function : Up, Down
[SAS;A] Source Active State A (Active State Clock) : High (rising), Low (falling),
Both (rising & falling)
Output Value
Error
Source AValue
Source BValue
Counter
Overview
Instances - 24 per RMS
Function
Source Active State A
Source Active State B
Source Function A
Source Instance A
Source Zone A
Source Error A
Source Function B
Source Instance B
Source Zone B
Source Error B
Load Value
Target Value
Latching
Count
[`Ctr]
[`SEt]
Counter Menu
Operation Page
[`Ctr]
[`SEt]
Counter Menu
Setup Page
Counter Operation:
Whenever a prescribed clock transition occurs with-
out an error on source B the count will be equal to
the Load Value.
Up Counter:
Whenever a prescribed clock transition occurs with-
out an error on Source B the count will increment by
+1. If the count is equal to 9,999 when the transition
occurs count will be 1 after transition.
Down Counter:
Whenever a prescribed clock transition occurs with-
out an error on Source B the count will decrement by
-1. If the count is equal to 0 when the transition oc-
curs the count will be 9,999 after transition.
An error, when read, can indicate any of the follow-
ing:
None, Open, Shorted, Measurement Error, Bad Cal
Data, Ambient Error, RTD Error, Fail, Math Error,
Not Sourced, Stale
Variable Function
Variable
Overview
Instances - 24 per RMS
Data Type
Digital Value
Analog Value
[o;u] Output Value : -1,999.000 to 9,999.000 or
On or Off
[Unit] Units : None, Absolute Temperature,
Relative Temperature, Power, Process,
Relative Humidity
Units
[tyPE] Data Type : Analog, Digital
[Dig] Digital Value : On, Off
[AnLg] Analog Value : -1,999.000 to 9,999.000
[`uAr]
[`SEt]
Variable Menu
Setup Page
Output Value
Error
Function passes stored value to output.
An error, when read, can indicate any of the following:
None, Open, Shorted, Measurement Error, Bad Cal
Data, Ambient Error, RTD Error, Fail, Math Error,
Not Sourced, Stale
Variable
Digital
Data Type
Digital Value
Analog Value
Units
Output Value
Error
Variable
Analog
Data Type
Digital Value
Analog Value
Units
Output Value
Error