Parameters
5.24 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/Off
ON
Error Group – Setup
Input Error Action (see also Input Group)
• Select how the controller responds to an input error.
• Read/write
• Modbus: 902
Range
0: bumpless transfer (control output power remains constant,
Chapter 4)
1: switch to the Fixed Manual Output (Control Output Group)
setting
2: shut off output
Default
0: bumpless transfer
Active
always
Error Clearing Mode
• Set the error clearing mode. When errors are latched, the error
message or indicator persists until it has been cleared manually.
Otherwise the error message or indicator clears automatically
when the condition that caused it no longer exists.
• Read/write
• Modbus: 607
Range
0: not latched (errors clear automatically)
1: latched (errors must be cleared manually)
Default
0: errors clear automatically
Active
always
Error Group continued