Watlow MICRODIN Manual de usuario Pagina 35

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 106
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 34
Power Limit
A high side power limit and low side power limit set the maximum output power
within two ranges
A low side power limit limits the output to a percentage of the maximum output
power while the process temperature or value is below the power limit set point.
The high side power limit limits the output to a percentage of the maximum output
power while the process temperature or value is above the power limit set point.
The low side power limit can be viewed or changed with Low Side Power Limit
(Control Output Group).
The high side power limit can be viewed or changed with High Side Power Limit
(Control Output Group).
The power limit set point can be viewed or changed with Power Limit Set Point
(Control Output Group).
The actual output power can be viewed with Output Power (Control Output
Power Group).
Figure 4.3 — Power Limits
Watlow MicroDIN 4.3
Time
Temperature
Process Temperature with power limit
Range Low
Range High
Process
Set Point
Power Limit Set Point
(between Range Low
and Range High)
Output Power is limited to 
Low Side Power Limit
Output Power switches
to High Side Power Limit
Process temperature
with no power limit