Parameters
=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.5
ON
Input Group continued
Input Group – Setup
Sensor Type
• Select the input sensor type.
• Read/write
• Modbus: 600
Range
0: thermocouple
1: RTD
Default
0: thermocouple
Active
always
Affects
Changes Input Type (Input Group) to J for thermocouple, DIN
for RTD, and defaults temperature related parameters.
Input Type
• Set the linearization for the input sensor.
• Read/write
• Modbus: 601
Range
if Sensor Type (Input Group) set to thermocouple
0: J
1: K
2: T
3: E
4: N
5: C
6: D
7: PT2
8: R
9: S
10: B
if Sensor Type (Input Group) set to RTD
11: RTD_DIN
12: RTD_JIS
Default
if Sensor Type (Input Group) is changed to thermocouple: J
if Sensor Type (Input Group) is changed to RTD: DIN
Active
always
Affected by
Changing Sensor Type sets to J for thermocouple, DIN for RTD,
and defaults temperature related parameters