Parameters
5.10 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/Off
ON
Control Output Group continued
Low Side Power
• Set the maximum allowed power below the Power Limit Set Point
(Control Output Group).
• Read/write
• Modbus: 715
Range
heat: 0.0 to 100.0
cool: -100.0 to 0.0
Default
heat: 100.0
cool: -100.0
Active
always
Affected by
Changing Control Output Function (Control Output Group)
changes range
Fixed Manual Output
• Select the initial control output power to take effect when the
controller is switched to manual mode by either the user or an
error.
• Read/write
• Modbus: 903
Range
heat: 0.0 to 100.0
cool: -100.0 to 0.0
Default
0.0
Active
always
Affected by
Changing Control Output Function (Control Output Group)
changes range