Users Manual
1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580
Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507 http://www.watlow.com
Registered Company
Winona, Minnesota USA
ISO 9001
TOTAL
3Year Warranty
CUSTOMER
SATISFACTION
Power Series
Microprocessor-Based
SCR Power Controller
U.S. English
Vista de pagina 0
1 2 3 4 5 6 ... 71 72

Indice de contenidos

Pagina 1 - Power Series

0600-0039-0000 Rev H Made in the U.S.A.July 2012 $10.00Supersedes: 0600-0039-0000 Rev GUser’s Manual1241 Bundy Boulevard, P.O. Box 5580, Winona, Minne

Pagina 2 - Your Comments

2.4 I Watlow Power Series Installation, Chapter 2Removing the Power SeriesController1. To release the Power Series controller from the mounting plate,

Pagina 3 - Table of Contents

Power Series Output Rating CurvesFan Cooled All curves are at 100% on with 90°C rated load wire and line wire connected. Note that eachchart is slight

Pagina 4

Power Series Output Rating CurvesNatural Convection All curves are at 100% on and with 90°C rated load wire and line wire connected. Note that each ch

Pagina 5 - Overview

Chapter ThreeWiringWiring the Power Series ControllerWiring options depend on the model number. Check the terminal designation stickers on theright si

Pagina 6 - Heater Diagnostics

3.2 Watlow Power Series Wiring, Chapter 3ç∫WARNING:To avoid damage toproperty and equipment,and/or injury or loss oflife, use National ElectricCode

Pagina 7 - Installation

Wiring, Chapter 3 Watlow Power Series 3.3Figure 3.3a – Single Zone Input WiringFigure 3.3b – 2-Zone Input WiringFigure 3.3c – 3-Zone Input WiringPow

Pagina 8 - Power Series Dimensions

3.4 Watlow Power Series Wiring, Chapter 3Line Power/Output WiringFigure 3.4a – Single Phase Output Wiring (Model PC1X-XXXX-XXXX)Figure 3.4b – 3 Phas

Pagina 9 - Harsh Environment

L2L1L3456Limit ControlContacts(If Required)Heater2Gnd1 34 5 6On-boardSemiconductor FusesFigure 3.5a – 3-Phase, 3-Leg,6-SCR Output Wiring for4-Wire Wye

Pagina 10 - Maintaining the Power Series

3.6 I Watlow Power Series Wiring, Chapter 3Wiring ExampleFigure 3.6 - System wiring example.Recommended fusing options to meet 200KA SCCR. All other u

Pagina 11 - Fan Cooled

Chapter FourNavigation and SoftwareKeys and DisplaysThis chapter explains keys, displays and navigation skills. You’ll also find a completesoftware ma

Pagina 12 - Natural Convection

Safety Information in this ManualNote, caution and warning symbols appear throughout this book to draw yourattention to important operational and safe

Pagina 13 - Chapter Three

Navigating the Power SeriesChoose a page (Setup or Factory) and press its key sequence. The page appears in the lowerdisplay.PressÎ or Ó to find a spe

Pagina 14 - Input Wiring

Navigation¬®[````]¬®[````]¬®[load]¬®[freq]¬®Single-Zone Single-Phase¬®[In``] or [In|c] or [In|u] ¬®[`Out]¬®[`Hbt]¬%%% ®[`UoL]¬®[`Cur]¬®[`HUa]Multi-Z

Pagina 15 - 3-Zone Input Wiring

4.4 Watlow Power Series Navigation and Software, Chapter 4**NOTE: These menus and display prompts are only viewable in the Factory Mode using a pass

Pagina 16 - Line Power/Output Wiring

Chapter FiveControl Methods and FeaturesFeatures, Chapter 5 Watlow Power Series 5.15Zero cross (also known as burst firing) provides evenoutput powe

Pagina 17 - Multizone Output Wiring

5.2 Watlow Power Series Features, Chapter 5Variable Time Base - Zero CrossIn the variable time base control method, an optimalratio of cycles on to

Pagina 18 - Wiring Example

Features, Chapter 5 Watlow Power Series 5.3Soft StartSoft start is a variation of phase angle controlexecuted on startup in which there is a gradual

Pagina 19 - Chapter Four

Heater BakeoutIf a system is shut down for long periods, someheaters can absorb moisture. With a standard powercontroller, turning the power full “on”

Pagina 20 - Navigating the Power Series

Watlow Power Series Features I 5.5Current LimitingThe current limit uses the RMS current entered bythe user. When a zone goes from 0.0% to a requested

Pagina 21 - Navigation

Baseline Voltage and Voltage CompensationThe baseline voltage is used by the controller toadjust the output so that the system power remainsconstant.

Pagina 22 - Setup Page Menus

Features, Chapter 5 Watlow Power Series 5.7Alarm StandardIf an alarm is configured as “standard” [`Std], thealarm indicators only occur while the al

Pagina 23 - Control Methods and Features

Chapter 1: Overview . . . . . . . . . . . . . . . . .1.1Chapter 2: Installation . . . . . . . . . . . . . . . .2.1Dimensions . . . . . . . . . . . .

Pagina 24 - Phase Angle

5.8 Features Watlow Power SeriesOverviewA Power Series controller can also be programmedand monitored by connecting it with a personalcomputer or pr

Pagina 25 - Maximum Rate of Change

Watlow Power Series Features 5.9RetransmitRetransmitting Output Load Current orLoad PowerThe retransmit feature allows an output toretransmit an ana

Pagina 26 - 100 75 50 25 0

5 .1 0 I F e at ur es W at lo w P owe r S er ie sSingle Phase ControlApply power to the line and the electronics powersupply. The displays will read [

Pagina 27 - Inductive Load Adjustment

Display LoopThe resting-state display shows one of the following sets of data, depending on controllersetup. The first prompt appears in the top displ

Pagina 28 - Other Features

Active if heater diagnostics optionis installed and heater bakeoutis running in the zone.157 r [1]167 r [2]n/a[9999] to [```0][minutes](9999 to 0)

Pagina 29 - [glbl] is used

Active with multizoneconfiguration.152 r [1]162 r [2]172 r [3]n/a[```0] to [9999] [V](0 to 9999) [Uol1], [Uol2], [Uol3]Line Potential(Volts) rmsRe

Pagina 30 - Communications

6.4 Watlow Power Series Parameters, Chapter 6Active with multiphaseconfiguration and heater diag-nostics option is installed.156 r n/a[```0] to [99

Pagina 31 - Retransmit

Setup PageTo enter the Setup Page, press the Home and Left keys (± ¬ ) together while in the Display Loop.Each of the following menus in the Factory

Pagina 32 - Fast Start Guide

Display Parameter Range Default Modbus Conditions for (Modbus Value) Address Parameters to Appearread/write6.6 Watlow Power Series Parameters, Chapt

Pagina 33 - Parameters

Display Parameter Range Default Modbus Conditions for (Modbus Value) Register Parameters to Appearread/writeParameters, Chapter 6 Watlow Power Series

Pagina 34

ii Watlow Power Series Table of Contents

Pagina 35

Active if heater diagnostics isinstalled.Active unless controller is 3phase, 2 leg configuration.Active if [`Hbo] is set to [``On].5116 r/w [1]5216 r/

Pagina 36

Active if heater diagnostics isinstalled.Active unless Input/Output con-figuration is 3 phase, 2-leg.Active if [algo] is set to [ph2t]and [Indf] is se

Pagina 37 - Setup Page

Active if [glbl] is set to [`Off].863 r/w[`std]active (0)[`std] active (0)[`LaT] latched (1)[`SIl] silenced (2)[LaSI] latched andsilenced (3)[Line] Li

Pagina 38

Active if communications isinstalled.Active if [glbl] is set to [`Off].869 r/w[`std]active (0)[`std] active (0)[`LaT] latched (1)[`SIl] silenced (2)[L

Pagina 39 - Methods and Features

Active if retransmit and heaterdiagnostics options are installed.871 r/w[`CUr] cur-rent (1)[`Off] none (0)[`CUr] current (1)[`HUA] kVA (2)[type] Retra

Pagina 40

Active if retransmit and heaterdiagnostics options are installed.Active if [`Cfg] is set to [`nna].883 r/w[2)00](2000)[rt|C_] to [2)00](Retransmit Out

Pagina 41

6.14 Watlow Power Series Parameters, Chapter 6[dATA] System Data Manipulation[`Loc] Global/Menu Lockouts[Info] Unit Information[diag] Diagnostics[`p

Pagina 42

*NOTE: These prompts (Backup, Default, and Restore Data Set) allow the user to manipulate the EEPROM contents.See Appendix, p. A.7, for more informati

Pagina 43

Active if [glOC] is set to [`Unl].Active if retransmit and heaterdiagnostics options areinstalled.1357 r/w [`Unl] (0)[`Unl] Unlocked (0)[`LOC] Locked

Pagina 44

Parameters, Chapter 6 Watlow Power Series 6.17NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter

Pagina 45

1Overview, Chapter 1 Watlow Power Series 1.1Chapter OneOverviewIntroductionThe Power Series is a state-of-the-art microprocessor-based Silicon Contr

Pagina 46 - Factory Page

Active: Always.1961 rn/a[```0] to [9999](0 to 9999)[HrS_] Accum Hours(0 - 9999)Accumulated systemoperating time(hours).Active: Always.Masked if hours

Pagina 47

* Values 0 to 4095Active for line on which line lossalarm has occurred since powercycle.1540 r1543 r1546 r1541 r1544 r1547 r1542 r1545 r1548 r{none] (

Pagina 48

Active if factory password isvalid.1700 r/w[`Off] idle(0)[`Off] idle (0)[`req] request factorymode (1)[`act] factory modeactive (2)[fcty] Factory Mode

Pagina 49 - [InFo] Unit Information Menu

Watlow Power Series Parameters 6.21NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Feat

Pagina 50

6.22 Parameters Watlow Power SeriesDisplay Parameter Range Default Modbus Conditions for (Modbus Value) Address Parameters to Appearread/write*NOTE:

Pagina 51 - [diAg] Diagnostics Menu

Appendix Watlow Power Series A.1AppendixATroubleshooting . . . . . . . . . . . . . . . . . . .A.2Troubleshooting Alarms and Errors . . . .A.4Checki

Pagina 52 - Factory Mode

All Units• If the controller has heater diagnostics installed, ashorted SCR will cause an error and shut down theremaining good SCRs. Return the unit

Pagina 53

Appendix Watlow Power Series A.3All Units (continued)Single Phase UnitsMultizone Units3 Phase, 2-Leg Units3 Phase, 3-Leg Units• For 3 phase, 3 groun

Pagina 54

[`alr] Communications[Cdog] Watchdog AlarmAlarm will occur if no communications is detected for time specified in [`Out] Watch-dog timeout. Not availa

Pagina 55 - Appendix

190 r/w(0-4)*Insure that the source of communications to the unit is communicatingwithout long interruptions. Verify the integrity of the communicatio

Pagina 56 - Troubleshooting

Single PhaseThis configuration can be purchased with any or all the features available on the PowerSeries. The only limitations are the features selec

Pagina 57 - 3 Phase, 3-Leg Units

A.6 I Watlow Power Series AppendixAnalog to digital failure error.Condition For Alarm or Error To OccurAlarm / Error[`err] System Errors Heater Bakeou

Pagina 58 - Alarm / Error

Power Series BackupThere are three prompts which allow the user to manipulate theEEPROM contents: Backup Data Set, Default Data Set, and RestoreData S

Pagina 59

A.8 Watlow Power Series Appendix1 Unit Serial Number High Digits2 Unit Serial Number Low Digits4 Software Version5 Manufactured Date (yymm)7 Hardwar

Pagina 60 - Checking and Replacing Fuses

Digital Programmer/Display andCommunications Capabilities• Programming functions• Adjust input and output control type, alarms and soft start. Heater

Pagina 61 - Power Series Backup

A.10 I Appendix Watlow Power SeriesOrdering Information(1528)To order, complete the code numberto the right with the information below:P C _ _ - _ _ _

Pagina 62 - Modbus Register Numbers

Appendix Watlow Power Series A.11Index AA to D Failure Error A.4Accum Hours (0 - 9999) 6.18Accum Hours (10K - 100M) 6.18Active Alarms 6.1Active

Pagina 63 - Specifications (2214)

A.12 Appendix Watlow Power SeriesLoad Power (kVA) Zone 2 6.3, 6.4 Load Power (kVA) Zone 3 6.4 Load Type Select (Control Zone 1only, 3 phase only

Pagina 64 - Ordering Information

Appendix Watlow Power Series A.13Prompt IndexA[``Ad] Select Analog to Digital Channel 6.19[Addr] Unit Address Select 6.12[ALÇ`] Heat Sink Alarm Te

Pagina 65

A.14 I Appendix Watlow Power Series%FDMBSBUJPO PG $POGPSNJUZ1PXFS 4FSJFT 1PXFS $POUSPMMFS8"5-08 8JOPOB *OD #VOEZ #PVMFWBSE8JOPOB .JOOFTPUB

Pagina 66

Watlow Power Series Appendix A.15Erforderliche Entstörfilter gemäß EN 61326 fürPower Series mit Laststrom ≥ 6A.Ein externer EMI-Filter sollte mit de

Pagina 67 - Prompt Index

Chapter TwoInstallationInstallation, Chapter 2 Watlow Power Series I 2.12The following two chapters will explain how to install the Power Series contr

Pagina 68 - %FDMBSBUJPO PG $POGPSNJUZ

A.16 Appendix Watlow Power SeriesDisplay Loop(See the Power Series User’s Manual)Setup Page[algo] Control Algorithm[ALgo] Power Control Algo Select

Pagina 70 - Power Series Software Map

Using the ManualWatlow Power Series User’s ManualWatlow Winona, 1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580,Phone: +1 (50

Pagina 71

2.2 I Watlow Power Series Installation, Chapter 2Mounting the Power Series ControllerNOTE: The Power Series controller must be mounted vertically. Whe

Pagina 72 - How to Reach Us

Installation, Chapter 2 Watlow Power Series 2.3Enclosure GuidelinesThe Power Series must be mounted in a suitable electrical enclosure. It musthave