Watlow MICRODIN Manual de usuario Pagina 1

Busca en linea o descarga Manual de usuario para Sensores Watlow MICRODIN. Watlow MICRODIN User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 106
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
MICRODIN
Communicating Subpanel Temperature Controller
W0UD-XUMN Rev A Made in the U.S.A.
January 1997 $10
Users Manual
User Levels:
• New User ....................................................... go to page 1.1
• Experienced User .......................................... go to page 2.1
• Expert User .................................................... go to page 2.1
Installers:
• Set-up ............................................................ go to page 2.1
• Wiring & Installation ........................................go to page 3.1
Controls
1241 Bundy Blvd., P.O. Box 5580, Winona, MN USA 55987-5580, Phone: (507) 454-5300, Fax: (507) 452-4507
Registered Company
Winona, Minnesota USA
ISO 9001
97
TOTAL
3 Year Warranty
CUSTOMER
SATISFACTION
Vista de pagina 0
1 2 3 4 5 6 ... 105 106

Indice de contenidos

Pagina 1 - User’s Manual

MICRODINCommunicating Subpanel Temperature ControllerW0UD-XUMN Rev A Made in the U.S.A.January 1997 $10User’s ManualUser Levels:• New User ...

Pagina 2 - Addendum

1.4 Watlow MicroDINOverviewNotes

Pagina 3 - Declaration of Conformity

AppendixA.14 Watlow MicroDINPrimary Control Output (heating or cooling)• Output update rate: 10 per second, 10Hz (maximum)Internal Load Switching (no

Pagina 4 - Meet the MicroDIN Team

AppendixWatlow MicroDIN A.15Ordering InformationTo order, complete the code number to the right with the information below:U D 1 A - 1 C E S - _ _ _ _

Pagina 5 - Your Feedback

AppendixA.16 Watlow MicroDINIndex 10-pin connector 3.5Aaccuracy A.14affects table 2.8Alarm Active Sides 5.20Alarm Condition 5.17Alarm High 5.19A

Pagina 6 - Table of Contents

AppendixWatlow MicroDIN A.17proportional control 4.8proportional integral control 4.9proportional integral derivativecontrol 4.10RRange High 4.6,

Pagina 7 - Chapter One:

AppendixA.18 Watlow MicroDINParameter Index(alphabetical order)AAlarm Active Sides 5.20Alarm Condition 5.17Alarm High 5.19Alarm Hysteresis 4.11, 5

Pagina 8

Watlow MicroDIN A.19AppendixUnits TypeC or FInput Error ActionControl Output FunctionSet Fixed Manual Output OOpen Loop DetectSensor TypeInput Type OR

Pagina 9 - Indicator Lights

Watlow MicroDIN User’s ManualWatlow Controls, 1241 Bundy Blvd., P.O. Box 5580, Winona, MN 55987-5580, Phone: (507) 454-5300, Fax: (507) 452-4507How to

Pagina 10 - Overview

Watlow MicroDIN 2.1CommunicationsSetupChapter Two:Communications Setup2Communications OverviewEIA-485 Network ... 2.2Modb

Pagina 11 - Communications Setup

2.2 Watlow MicroDINCommunications OverviewEIA-485 NetworkThe MicroDIN uses the EIA-485 (formerly, ÒRS-485Ó) hardware interface tocommunicate with thre

Pagina 12 - Communications Overview

EIA-485 NetworkThe MicroDIN EIA-485 (RS-485) Network CharacteristicsAn EIA-485 interface uses three wires in a half-duplex configuration.The EIA-485 s

Pagina 13 - EIA-485 Network

2.4 Watlow MicroDINSpecial Case 485 Network ConsiderationsIf your EIA-485 network does not work, it may require termination resistors.Termination Resi

Pagina 14 - Communication

Watlow MicroDIN 2.5CommunicationsSetupMicroDIN, A Modbus™Remote Terminal Unit (RTU)RTU The MicroDIN uses Modbus™RTU (remote terminal unit) protocol to

Pagina 15 - Remote Terminal Unit (RTU)

2.6 Watlow MicroDINCommunicationSetupModbus Register Numbers40001 0 Model Number (Diagnostics)40002 1 Serial Number (Characteristics)40003 2 Serial Nu

Pagina 16 - Modbus Register Numbers

Watlow MicroDIN 2.7CommunicationsSetupSet Address/Baud RateConfigure the communications speed and network address of the MicroDINcontroller with the e

Pagina 17 - Set Address/Baud Rate

CommunicationSetupNote: This table also appears inside the back cover, p. A.19Watlow MicroDIN 2.8Units TypeC or FInput Error ActionControl Output Fun

Pagina 18 - C D D C

Serial Data FormatConfigure your computer’s COM1 or COM2 (communications) port data formatto match the MicroDIN’s settings in the table below.MicroDIN

Pagina 19 - 8 None 1 1

PurposeTo meet Mark CE requirements, this addendum provides supplemental information to the MicroDIN User’s Manual (W0UD-XUMN Rev A), and the MicroDIN

Pagina 20

2.10 Watlow MicroDINCommunicationSetupNotes

Pagina 21 - Installation and Wiring

Install and WireWatlow MicroDIN 3.1Installation and Wiring Chapter Three:Installation and Wiring3Introduction Set DIPs First ...

Pagina 22 - Introduction

3.2 Watlow MicroDINIntroductionFor a successful MicroDIN installation you need to cover the tasks cited in thesubheads below. If you do all these thi

Pagina 23 - Figure 3.3

Watlow MicroDIN 3.3Install and WireMounting the MicroDINTo mount a MicroDIN on a DIN rail, hook the upper lip of the rail mountingbracket onto the rai

Pagina 24 - To Dismount MicroDIN

3.4 Watlow MicroDINInstall and WireMounting the MicroDIN on a DIN railTo Mount MicroDIN1. Push unit in and down to catch rail hookon top of rail.2. Ro

Pagina 25

Watlow MicroDIN 3.5Install and WireMicroDIN RJ-11 and 10-pin ConnectorsThe MicroDIN 10-pin screw terminal connector, on the bottom of the case, linksi

Pagina 26 - Input Wiring

3.6 Watlow MicroDINInstall and WireInput Wiring12345678910+-12345678910S1 S312345678910S1S2S3Figure 3.6b — Control Input, ThermocoupleFigure 3.6a — Mi

Pagina 27 - Output and Power Wiring

Watlow MicroDIN 3.7Install and WireOutput and Power Wiring12345678910+ExternalLoad-dc+COMdc-+-Power Supply60V max.1A max.12345678910ExternalLoadC

Pagina 28 - Communications Wiring

3.8 Watlow MicroDINInstall and WireCommunications WiringAddressPowerCommsAlarm Temperature ControllerMicroDINTemperature ControllerMicroDINControlOutp

Pagina 29

Watlow MicroDIN 3.9Install and WireSpecial EIA-485 Network ConsiderationsIf your MicroDIN network needs termination and pull-up and pull-downresistors

Pagina 30 - Wiring Examples

Declaration of ConformityWATLOW CONTROLS1241 Bundy BoulevardWinona, Minnesota 55987 USADeclares that the following product:EnglishDesignation: Series

Pagina 31

3.10 Watlow MicroDINInstall and WireWiring ExamplesHightemp.light92A3-1DJ1-DCLimit ControlHeaterOptionalNormallyOpenMomentarySwitchDIN-a-miteDA1C-1624

Pagina 32

Watlow MicroDIN 3.11Install and Wire111234567891011112222222222333344455566778889991010101111++++––––11181615141419172021121313High Temp. LightL1L1L2L

Pagina 33 - Features

3.12 Watlow MicroDINInstall and WireNotes

Pagina 34 - The System

Watlow MicroDIN 4.1FeaturesChapter Four:Features4The SystemAuto-tune ... 4.2Power Limit ...

Pagina 35 - Power Limit

4.2 Watlow MicroDINThe SystemAuto-tuneAuto-tuning allows the controller to explore the responsiveness of the system inorder to determine an effective

Pagina 36 - Calibration Offset

Power LimitA high side power limit and low side power limit set the maximum output powerwithin two rangesA low side power limit limits the output to a

Pagina 37 - Filter Time Constant

4.4 Watlow MicroDINInputCalibration OffsetCalibration offset allows a device to compensate for an inaccurate sensor, leadresistance or other factors t

Pagina 38 - Range Low and Range High

Filter Time ConstantA time filter smooths an input signal by sampling the input at designated timeintervals. Either the viewed value or both the viewe

Pagina 39 - Control Methods

4.6 Watlow MicroDINSensor SelectionYou need to configure a controller to match the input device, which is normally athermocouple or RTD. When you sele

Pagina 40 - Proportional Control

Control MethodsOn/Off ControlOn/off control switches the output either full on or full off, depending on theinput, set point and hysteresis values. Th

Pagina 41

Meet the MicroDIN TeamFront Row: Rob Hermann, board assembly; Gene Lauer, product manager; Keith Ness, engineering team leader;Steve Lubahn, group lea

Pagina 42

4.8 Watlow MicroDINProportional ControlSome processes need to maintain a temperature or process value closer to theset point than on/off control can p

Pagina 43 - Alarm Hysteresis

Proportional plus Integral (PI) ControlThe droop caused by proportional control can be corrected by adding integral(reset) control to the system. When

Pagina 44 - Alarm Latching

4.10 Watlow MicroDINProportional plus Integral plus Derivative (PID) ControlUse derivative (rate) control to minimize the overshoot in a PI-controlled

Pagina 45 - Alarm Silencing

Watlow MicroDIN 4.11FeaturesAlarmsAn alarm takes some action, usually notifying an operator, when the processtemperature leaves a defined range. A use

Pagina 46 - Open Loop Detect

4.12 Watlow MicroDINFeaturesProcess or Deviation AlarmsA process alarm uses one or two fixed set points to define an alarm condition.A deviation alarm

Pagina 47 - Bumpless Transfer

Watlow MicroDIN 4.13FeaturesAlarm SilencingAlarm silencing has two uses:1. It is often used to allow a system to warm up after it has been started up.

Pagina 48

4.14 Watlow MicroDINFeaturesErrorsPanel Indicator LightsError 4 RAM malfunction (return to factory)Error 5 EEPROM data corruptedError 6 PROM malfuncti

Pagina 49 - Learn the Parameters

Bumpless TransferWhen the sensor opens (fails), the MicroDIN switches from automatic to manualoperation.When transferring from automatic to manual ope

Pagina 50 - System Group

4.16 Watlow MicroDINNotesFeatures

Pagina 51 - System Group continued

Watlow MicroDIN 5.1ParametersChapter FiveLearn the Parameters5System Group ...5.2Ambient (CJC) Temperature (1500).5.2Non-volatile Memory (24)

Pagina 52 - Input Group

Safety InformationWe use note, caution and warning symbols throughout this book to draw yourattention to important operational and safety information.

Pagina 53 - Input Group continued

Parameters5.2 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/OffONSystem Group continuedSystem Group – MonitorSystem Error • See Err

Pagina 54

Parameters=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.3ONSystem Group – SetupUnits Type • Select US or SI units of measurement.• Read/wr

Pagina 55

Parameters5.4 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/OffONInput Group – MonitorInput Actual • Monitor the input value.• Duri

Pagina 56 - Control Output Group

Parameters=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.5ONInput Group continuedInput Group – SetupSensor Type• Select the input sensor ty

Pagina 57 - High Side Power

Parameters5.6 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/OffONRange Low • Set the input range low. This setting is the lowest va

Pagina 58 - Fixed Manual Output

Parameters=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.7ONFilter Time Constant • Set the filter time for the input, in seconds. This smoo

Pagina 59 - Operation Group

Parameters5.8 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/OffONControl Output Group – MonitorOutput Power• Monitor the control ou

Pagina 60 - Operation Group continued

ParametersControl Output Group continued=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.9ONRange0: heat1: coolDefault0: heatActivealwaysAffe

Pagina 61 - PID Group

Parameters5.10 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/OffONControl Output Group continuedLow Side Power• Set the maximum all

Pagina 62 - PID Group continued

Control Output Group continuedParameters=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.11ONOperation GroupMonitorOperation Mode ...

Pagina 63

iv Watlow MicroDINChapter 1: Overview ... 1.1Introduction to the MicroDIN Contr

Pagina 64

Parameters5.12 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/OffONOperation Group continuedUser Set Point• Change or monitor the co

Pagina 65

Parameters=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.13ONPID GroupMonitorPID Output Power ... 5.13Ini

Pagina 66 - Alarm Output Group continued

ParametersPID Group continued5.14 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/OffONInitiate Auto-tune• Initiate or cancel an auto

Pagina 67

Parameters=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.15ONPID Group continuedabout PID control.• Read/write• Modbus: 502Range0.00 to 99.

Pagina 68

Parameters5.16 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/OffONPID Group continuedCycle Time • Set the control output cycle time

Pagina 69

Parameters=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.17ONAlarm Output Group – MonitorAlarm Condition • Monitor the alarm state.• Read o

Pagina 70 - Error Group continued

Parameters5.18 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/OffONAlarm Output Hardware • Read the alarm output hardware type.• Rea

Pagina 71

Parameters=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.19ONAlarm Output Group continuedAlarm Output Group – SetupAlarm Low • Set the low

Pagina 72

Parameters5.20 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/OffONAlarm Output Function • Turn the alarm output on or off.• Read/wr

Pagina 73 - Characteristics Group

Parameters=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.21ONRange0: both1: high side only2: low side onlyDefault0: bothActiveif Alarm Outp

Pagina 74 - Software Revision

OverviewWatlow MicroDIN 1.1Chapter One:Overview1Introduction to the MicroDIN Controller .. 1.2Setup Steps ...

Pagina 75 - Diagnostics Group continued

ParametersError Group continuedError GroupMonitorOpen Loop Error ... 5.22Open Loop Detect ...

Pagina 76

Parameters=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.23ONInput Error (see also Input Group) • Monitor the input error status.• Read onl

Pagina 77

Parameters5.24 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/OffONError Group – SetupInput Error Action (see also Input Group) • S

Pagina 78 - Calibration Group continued

ParametersCharacteristics Group continued=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.25ONCharacteristics GroupDate of Manufacture ...

Pagina 79

Parameters5.26 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/OffONSerial Number 2 • Read the last four digits of the serial number.

Pagina 80

ParametersDiagnostics Group continued=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.27ONDiagnostics GroupModel Number ...

Pagina 81 - Operation and Calibration

Parameters5.28 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/OffONRTD Lead Compensation Analog-to-Digital Counts• Reads the raw, RT

Pagina 82 - MicroDIN Startup

Parameters=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.29ONDerivative Term • Monitor the derivative term. See Chapter 4 for information a

Pagina 83 - MicroDIN Shutdown

5.30 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/OffONParametersCalibration Group continuedEnter Calibration Mode• Enter calibrat

Pagina 84 - Operations

=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.31ONParametersRestore to Factory Calibration (Set)• Restore factory calibration values from

Pagina 85 - • See p. 5.6

Overview1.2 Watlow MicroDIN1.2 Watlow MicroDINIntroduction to the MicroDIN ControllerThe Watlow MicroDIN controller is a DIN rail-mounted, temperature

Pagina 86 - Setup and calibration

5.32 Watlow MicroDINParametersNotes

Pagina 87 - Appendix

Watlow MicroDIN 6.1OperationsChapter Six:Operation and Calibration6MicroDIN Startup ... 6.2MicroDIN Shutdown ...

Pagina 88 - Packet Syntax

6.2 Watlow MicroDINOperationsMicroDIN StartupStarting the Watlow MicroDIN for either one zone or severalin any thermal system requires successful comp

Pagina 89

MicroDIN ShutdownShutting down a Watlow MicroDIN-controlled thermal system for an optimumrestart requires attention to the following list:• Updating a

Pagina 90

6.4 Watlow MicroDINOperationsLED Indication Symptoms Probable Cause(s)Troubleshooting Alarms and Errors most likely problems are listed firstPower• No

Pagina 91 - Loop Back Command (0x08)

OperationsCorrective Action ReferenceWatlow MicroDIN 6.5• Check switches, fuses, breakers, interlocks, limits, connectors, • See Watlow Publication e

Pagina 92 - Exception Responses

6.6 Watlow MicroDINOperationsNote: For information on writing Modbus™ RTUcommunications software for MicroDIN, see theAppendix.To enter the calibratio

Pagina 93

Watlow MicroDIN A.1AppendixAppendixAModbus™RTU ... A.2Glossary ...

Pagina 94 - Glossary

A.2 Watlow MicroDINModbus Remote Terminal Unit (RTU)Modbus RTU enables a computer or PLC to read and write directly to registerscontaining the control

Pagina 95

Packet format: | nn | nn | nn nn…| nn nn |∆∆∆∆∆∆addresscommandregisters and/or dataCRCRead Multiple Registers Command (0x03 or 0x04)This command retur

Pagina 96

OverviewSetup Steps1. Set up communications.2. Set the controller’s address and baud speed with the DIP switches on the toppanel (see Chapter 2, Commu

Pagina 97

A.4 Watlow MicroDINExample: Read register 0 (model number) of the controller at address 1.Sent: 01 03 00 00 00 01 84 0AReceived: 01 03 02 03

Pagina 98

Packet sent to controller: | nn | 10 | nnnn | 00 01 | 02 | nnnn | nn nn |∆∆∆∆∆∆∆∆∆∆∆controller address (one byte)write to multiple registers command (

Pagina 99 - Output #2: User selectable

A.6 Watlow MicroDINExample: Run loop back test on controller at address 40 (0x28).Sent: 28 08 55 66 77 88 31 B7Received: 28 08 55 66 77 88

Pagina 100 - A.14 Watlow MicroDIN

Cyclical Redundancy Checksum (CRC) AlgorithmThis C routine, calc_crc(), calculates the cyclical redundancy checksum, CRC,for a string of characters.

Pagina 101 - Ordering Information

A.8 Watlow MicroDINGlossaryannunciator — A visual display that uses pilot lights to indicate the former orexisting condition of several items in a sys

Pagina 102 - 4.4, 5.6

a form A or form B contact. hysteresis — A change in the process variable required to re-energize thecontrol or alarm output. Sometimes called switchi

Pagina 103 - Watlow MicroDIN A.17

A.10 Watlow MicroDINproportional control — A control using only the P (proportional) value of PIDcontrol.range — The area between two limits in which

Pagina 104 - Parameter Index

transmitter — A device that transmits temperature data from either athermocouple or a resistance temperature detector (RTD) by way of a two-wireloop.

Pagina 105

Declaration of ConformityWATLOW CONTROLS1241 Bundy BoulevardWinona, Minnesota 55987 USADeclares that the following product:EnglishDesignation: Series

Pagina 106 - Quality and

AppendixWatlow MicroDIN A.13Specifications: W0UD-XSPN Rev A01Control Mode• Microprocessor-based, user selectable control modes• Single input, single o

Comentarios a estos manuales

Sin comentarios