Watlow MICRODIN Manual de usuario Pagina 50

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 106
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 49
Parameters
5.2 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/Off
ON
System Group continued
System Group – Monitor
System Error
• See Error Group.
Ambient (CJC) Temperature
• Read the ambient temperature in 0.1 degrees Fahrenheit.
• Read only
• Modbus: 1500
Range
0.0 to 180.0 F
Default
none
Active
always
System Group – Use
Non-volatile Memory
• Disable storage of parameters to non-volatile (EEPROM) memory.
This allows you to change parameters frequently without wearing
out the memory.
• Read/write
• Modbus: 24
Range
0: store parameters when they are changed
1: do not store parameters when they are changed
Default
0 (always reverts to 0 when the controller’s power is turned off
and on)
Active
always
Affects
all parameters
will not save any parameters when set to 1.
ç
CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
See Disable Non-
volatile Memory
(System Group).
System Group
Monitor
Ambient (CJC) Temperature .................... 5.2
Use
Non-volatile Memory ................................. 5.2
Setup
Units Type ................................................. 5.3
C or F ......................................................... 5.3
Decimal Point ............................................ 5.3
Vista de pagina 49
1 2 ... 45 46 47 48 49 50 51 52 53 54 55 ... 105 106

Comentarios a estos manuales

Sin comentarios