Parameters
5.18 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/Off
ON
Alarm Output Hardware
• Read the alarm output hardware type.
• Read only
• Modbus: 17
Range
1: mechanical relay
Default
1
Active
always
Alarm Output Group – Use
Clear Alarm
• Alarm will clear if alarm condition is resolved
• Read/write
• Modbus: 331
Range
0: no action
1: try to clear a latched alarm
Default
0 (always reverts to 0 after a write)
Active
if Alarm Latching Mode (Alarm Output Group) is set to yes
Silence Alarm
• Silence the alarm manually.
• Read/write
• Modbus: 332
Range
0: no action
1: silence alarm
Default
0 (always reverts to 0 after a write)
Active
always
ON
ON
Alarm Output Group continued