Watlow EZ-ZONE
®
RME Module 95 Chapter 6 Features
Digital Input/Output Function
Note:
Input value is passed to any specified digital input source
when programmed as input by that function block.
Output value determine by Function Block driving this
output.
Digital I/O Value : On, Off
An error, when read, can indicate any of the following:
None, Open, Shorted, Measurement Error, Bad Cal Data,
Ambient Error, RTD Error, Fail, Math Error, Not Sourced,
Stale
Output Function
Output Function Instance
Source Zone A
Output Low
Power Scale
Output Time Base
Output Control
Output High
Power Scale
Direction
[`S2;A] Source Zone A : 0 to 16
[`do;S] Output State : On, Off
[`o;Ct] Output Control : Fixed Time Base, Variable Time Base
[`o;Lo] Output Low Power Scale : 0.0 to 100.0 %
[`dir] Direction : Output, Input Contact, Input Voltage
[`o;hi] Output High Power Scale : 0.0 to 100.0 %
[`o;tb] Output Time Base : 0.1 to 60.0 seconds
[``Fi] Output Function Instance : 1 to 250
[`di;S] Input State : On, Off
Output State
Digital I/O Value
Error
[`dio] Digital I/O Menu
[`SEt] Operation Page
[`dio] Digital I/O Menu
[`SEt] Setup Page
[``Fn] Output Function : Off, Analog Input, Alarm, Cool Power, Heat
Power, Compare, Counter, Digital I/O, Profile Event Out A to H,
Function Key, Logic, Linearization, Math, Process Value, Special
Function Output 1 to 4, Timer, Variable
Digital IO
Overview
Instances - 0, 6, 12, 18 or 24 per RME
Digital IO as Input
Input State
Digital I/O Value
Error
Digital Input Value
Output Low Power Scale
Output Time Base
Output Control
Output High
Power Scale
Direction
Output Function
Output Function Instance
Source Zone A
Output Low Power Scale
Output Time Base
Output Control
Output High Power Scale
Direction
Output State
Digital I/O Value
Error
Digital IO as Output
Global Function
This function allows the user to change display units
as well as save and restore user settings.
Global
Overview
Instances - 1 per RME
[AC;Lf] AC Line Frequency : 50 Hz, 60 Hz
[d;PrS] Display Pairs : 1 to 10
[USr;S] User Settings Save : None, User Set 1, User Set 2
[USr;r] User Settings Restore : None, User Set 1, User Set 2, Factory
[`C_F] Display Units : F, C
AC Line Frequency
User Settings Restore
Display Units
User Settings Save
Display Plairs
[gLbL] Global Menu
[`SEt] Setup Page
Output Value
Linearization Function
This function will take an analog Source A and re-
linearize using a 10-point offset, then add Offset and
produce an Output Value.
An error, when read, can indicate any of the follow-
ing: None, Open, Shorted, Measurement Error, Bad
Cal Data, Ambient Error, RTD Error, Fail, Math Er-
ror, Not Sourced, Stale
Linearization
Overview
Instances - 8 per RME
Units
Function
Input Point 1
Output Point 1
Output Point 2
Output Point 3
Output Point 4
Output Point 5
Output Point 6
Output Point 7
Output Point 8
Output Point 9
Output P
oint 10
Offset
Input Point 2
Input Point 3
Input Point 4
Input Point 5
Input Point 6
Input Point 7
Input Point 8
Input Point 9
Input Point 10
[SFn;A] Source Function A : None, Analog Input, Current, Cool Power, Heat Power,
Power, Linearization, Math, Process Value, Set Point Closed, Set Point Open, Variable
[`S2;A] Source Zone A : 0 to 16
[`Si;A] Source Instance A : 1 to 250
[``Fn] Function : Off, Interpolated, Stepped
[`iP;1] Input Point 1 : -1,999.000 to 9,999.000
[`iP;2] Input Point 2 : -1,999.000 to 9,999.000
[`iP;3] Input Point 3 : -1,999.000 to 9,999.000
[`iP;4] Input Point 4 : -1,999.000 to 9,999.000
[i`P;5] Input Point 5 : -1,999.000 to 9,999.000
[`iP;6] Input Point 6 : -1,999.000 to 9,999.000
[`iP;7] Input Point 7 : -1,999.000 to 9,999.000
[`iP;8] Input Point 8 : -1,999.000 to 9,999.000
[`iP;9] Input Point 9 : -1,999.000 to 9,999.000
[iP;10] Input Point 10 : -1,999.000 to 9,999.000
[`oP;1] Output Point 1 : -1,999.000 to 9,999.000
[`oP;2] Output Point 2 : -1,999.000 to 9,999.000
[`oP;3] Output Point 3 : -1,999.000 to 9,999.000
[`oP;4] Output Point 4 : -1,999.000 to 9,999.000
[`oP;5] Output Point 5 : -1,999.000 to 9,999.000
[`oP;6] Output Point 6 : -1,999.000 to 9,999.000
[`oP;7] Output Point 7 : -1,999.000 to 9,999.000
[`oP;8] Output Point 8 : -1,999.000 to 9,999.000
[`oP;9] Output Point 9 : -1,999.000 to 9,999.000
[oP;10] Output Point 10 : -1,999.000 to 9,999.000
[Unit] Units : Source, None, Absolute Temperature, Relative Temperature, Power,
Process, Relative Humidity
[`Lnr] Linearization
[`SEt] Setup Page
Source Function A
Source Instance A
Source Zone A
Source Error A
Output Value
Source Value A
Error