Watlow EZ-ZONE
®
RME Module • 43 • Chapter 4 Setup Page
RME Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
&
Read/
Write
[sfn;A]
[SFn.A]
Action (1 to 8)
Source Function A
Set the event or function
that will trigger the action.
[nonE] None (61)
[ALM] Alarm (6)
[`CPE] Compare (230)
[`Ctr] Counter (231)
[`dio] Digital I/O (1142)
[Ent;A] Profile Event Out
A (233)
[Ent;b] Profile Event Out
B (234)
[Ent;C] Profile Event Out
C (235)
[Ent;d] Profile Event Out
D (236)
[Ent;E] Profile Event Out
E (247)
[Ent;F] Profile Event Out
F (248)
[Ent;g] Profile Event Out
G (249)
[Ent;h] Profile Event Out
H (250)
[`FUn] Function Key
(1001)
[lim] Limit (126)
[`lgC] Logic (239)
[tMr] Timer (244)
[`uAr] Variable (245)
None 1290
[offset 20]
0x6E (110)
1 to 8
6
- - - - 10006 uint
RWES
[`si;a]
[ Si.A]
Action (1 to 8)
Source Instance A
Set the instance of the
function selected above.
1 to 250 1 1282
[offset 20]
0x6E (110)
1 to 8
2
- - - - 10002 uint
RWES
[`52;A]
[ SZ.A]
Action (1 to 8)
Source Zone A
Set the zone of the function
selected above.
0 to 16 0 1292
[offset 20]
0x6E (110)
1 to 8
7
- - - - 10007 uint
RWES
[`LEu]
[ LEv]
Action (1 to 8)
Active Level
Set the action that will be
considered a true state.
[LoW] Low (53)
[high] High (37)
High 1280
[offset 20]
0x6E (110)
1 to 8
1
137 10001 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set