
Watlow EZ-ZONE
®
RME Module • 54 • Chapter 4 Setup Page
RME Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
&
Read/
Write
[`Er;h]
[ Er.h]
Compare (1 to 8)
Error Handling
Use Error Handling to
select the output value and
error output state of this
function if it receives an er-
ror signal from one or more
sources and it cannot de-
termine the output value.
[``t;g] True Good (1476)
[``t;b] True Bad (1477)
[``F;g] False Good (1478)
[``F;b] False Bad (1479)
False Bad 4002
[offset 40]
0x80 (128)
1 to 8
0x0C (12)
- - - - 28012 uint
RWES
[tMr]
[`Set]
Timer Menu
[``Fn]
[ Fn]
Timer (1 to 8)
Function
Set how the timer will
function.
[`oFF] Off (62)
[`on;P] On Pulse (1471)
[`dEL] Delay (1472)
[``o;s] One Shot (1473)
[`rET] Retentive (1474)
Off 4956
[offset 50]
0x83 (131)
1 to 8
9
223 31009 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set
Comentarios a estos manuales