Watlow EZ-ZONE
®
RME Module 25 Chapter 2 Install and Wire
Warning: ç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices. Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life.
Note:
Maximum wire size termination
and torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12
AWG) single-wire termination
or two 1.31 mm
2
(16 AWG)
• 0.8 Nm (7.0 in-lb.) torque
Note:
Adjacent terminals may be la-
beled differently, depending on
the model
number.
Note:
To prevent damage to the con-
troller, do not connect wires to
unused terminals.
Note:
Maintain electrical isolation
between digital input-outputs,
switched dc/open collector out-
puts and process outputs
to
prevent ground loops.
Note:
If the last two digits of the part
number are "12", this equip-
ment is suitable for use in
CLASS I, DIVISION 2, Groups
A, B, C and D or Non-Hazard-
ous locations
only. Temperature
Code T4
Warning: ç
Explosion Hazard – Substitution of
component may impair suitability for
CLASS I, DIVISION 2.
Warning: ç
Explosion Hazard - Do not disconnect
while the circuit is live or unless the
area is known to be free of ignitable
concentrations of flammable sub-
stances.
Standard Bus EIA-485 Communications
T-/R-
common
Slot C
T+/R+
98 99 CF CD CE CZ CX CY
Wire T-/R- to the A ter-
minal of the EIA-485
port.
Wire T+/R+ to the B
terminal of the EIA-485
port.
Wire common to the
common terminal of the
EIA-485 port.
Do not route network
wires with power wires.
Connect network wires
in daisy-chain fashion
when connecting mul-
tiple devices in a net-
work.
A 120 Ω termination re-
sistor may be required
across T+/R+ and T-/R-,
placed on the last con-
troller on the network.
Do not connect more
than 16 EZ-ZONE RM
controllers on a net-
work.
• maximum network
length: 1,200 meters
(4,000 feet)
1/8th unit load on EIA-
485 bus
S
l
o
t
C
98 99
CF CD CE CZ CX CY
98 99
CF CD CE CZ CX CY
Use twisted pair wires such as Cat 5 cabling.
Do not route with power carrying conductors.
LINX
Model 485TB-2W
U
S
B
A(-)
A(-)
B(+)
B(+)
GND
B B electronics
&
TM
U
USB Serial Conversion
0847-0326-0000
EZ-ZONE
®
RM
to B&B Converter
Model ULINX 485USBTB-2W
USB to RS-485 Adapter
using Standard Bus
TM
USB
Port
Data format
38,400 baud
8 data bits
no parity
1 start bit
1 stop bit
PC Software Protocol - Standard Bus
EZ-Configurator
Note:
Do not leave a USB to EIA-485 converter connected to Standard Bus without
power (i.e., disconnecting the USB end from the computer while leaving the
converter connected on Standard Bus). Disturbance on the Standard Bus may
Vista de pagina 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 123 124

Comentarios a estos manuales

Sin comentarios