Watlow Series 935A Users Manual 23
To Set Up Front Panel Lock
1. Install an external switch.
2. Wire the control per the example below and the information on p. 42-45.
3. Go to [CnFG], then [`Ot1], and choose [`FPL].
Table 9 - Using Front Panel Lock
Figure 6 - Front Panel Lock Wiring
See p. 43 for more wiring information.
(Closed switch = locked)
WARNING: When Output 1 is a Front Panel Lock [`Ot1] = [`FPL], the output is energized! Do
not connect a power switching device to Output 1; injury or death, or damage to equipment or
property could result.
ç
CAUTION: Failure to install a 60 to 70, 0.5 watt resistor across the customer-supplied Front
Panel Lock switch will cause the panel to lock out even when the switch is open. Injury to
personnel, or damage to equipment or property could result.
Out
p
ut 1; Front Panel Lock
S2
1
S1
+
2
3
+
45678
OT1IN OT2
POWER
60 to 70 0.5w resistor See Caution
Configuration Menu
[``In]
Input Type
[`C_F]
Celsius/Fahrenheit
[``rL]
Input Range Low
[``rh]
Input Range High
[`Ot1]
Output 1 Function
[`Ot2]
Output 2 Function
[dISP]
Display Default
[FAIL]
Failure Mode
[tIM
Timer Function
[Strt]
Start Timer
[`rdY]
Timer Ready Band
[``St]
Signal Time
[SLOC]
Set Point Lockout
[`tAG]
Lockout Tag
[`Ot1] [`FPL]
Set Up Front Panel Lockout
[`Ot1] = [`FPL]
View Process Yes
View Set Point Yes
Change Set Point No
Auto-tune No
Reset Alarm Yes
View or Change Operation No
Menu (Except Config. Menu)
View or Change Configuration No
Menu (Except Tag)