Watlow Series 935A Manual de usuario Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 68
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
Watlow Series 935A Users Manual 15
Set-Up General
Integral Function - Select an integral value.
[`)00] [9(99]
0.00 to 99.99 minutes/repeat
Derivative Function - Select a derivative value.
[`)00] [`(99
0.00 to 9.99 minutes
Calibration Offset - Select a calibration offset value.
[-999]] [9999] [-9(9] [99(9
-999° to 9999°F or C or -99.9° to 999.9°F or C
Note: Access to the PID Menu and the prompts there varies with lockout function and output set-up. The PID Menu is
locked out when the 935A leaves the factory.
Lockout function; the Lockout Tag [`tAg] function masks menus from view (if you cannot see a prompt, you can make no
change). See Using Lockout Functions, p. 18.
Output set-up; you must choose [hEAt] or [COOL] in either Output 1 or Output 2 to have access to the PID Menu. With a
[hEAt] only choice, [COOL] prompts are not visible, and vice versa. See the Valid Output Functions Table, p. 3, or Setting Up
Inputs and Outputs, p. 20.
[``It]
[``dE]
[`CAL]
Vista de pagina 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 67 68

Comentarios a estos manuales

Sin comentarios