Watlow Series 935A Users Manual 17
NOTE:
Access to Configuration Menu varies with lockout function. See p. 19.
Alarm Hysteresis - Choose alarm switching band.
[```1[ [`999] [```1] [`555] [``)1] [99(0] [``)1] [55%0]
1°F to 999°F, or 1°C to 555°C, or 0.1°F to 999.0°F, or 0.1°C to 555.0°C
Alarm Latch - Choose latching or non-latching alarms.
A latching alarm requires a ß press to clear it after the alarm condition clears.
[``no] [`YES]
NO YES
Alarm Silencing - Choose to silence alarms on startup, or not.
[`SIL] = [`YES] silence an alarm with a ß press.
[``no] [`YES
NO YES
Failure Mode - Choose output action after a sensor failure.
Bumpless transfer provides a smooth transition to percent power control without output state change.
[bPLS] [-100] [`100]
Bumpless Percent Power
Timer Output Function - Choose output function for the end of the timer.
Delay ON = Turn ON, Delay Off = Turn off, Signal ON = Toggle ON, Signal off = Toggle off
[dLon] [dLoF] [SGon] [SGof]
Delay Delay Signal Signal
on Off On Off
Start Timer Function - Choose the start timer conditions:
[IMd] = Immediate start on a , press; [`rdy] = , press and Actual temp. is inside the Ready Band;
[rdYA] = , press, plus Actual temp. is inside the Ready Band, then acknowledge with a ß press;
[PWr] = immediate start on power-up without waiting for the Ready Band temp. or a , press.
[IMd] [`rdY] [rdYA] [PWr]
Immediate Ready Ready Power
Acknowledge
Timer Ready Band - If [Strt] =[`rdY] or [rdYA], select ready band high/low values.
[```0] [`999] [```0] [`555] [``)0] [99(0] [``)0] [55%0]
0°F to 999°F, or 0°C to 555°C, or 0.0°F to 999.0°F, or 0.0°C to 555.0°C
Signal Time - If [tIM] = [SGon] or [SGoF], select a Signal ON or Signal off time duration to trigger an annunciator or other action at completion of
countdown time.
[```1] [9959]
1 sec. to 99:59 min:sec.
Set Point Lock - Choose to lock the Primary Set Point from change, not view.
[``no] [`YES]
NO YES
Lockout Tag - Choose undisplayable/unchangeable menus; [PCOA] = all locked.
[PCOA] [PCO`] [PC`A] [PC``] [P`OA] [P`O`] [P``A] [P```]
[`COa] [`CO`] [`C`A] [`C``] [``OA] [``O`] [```A] [````]
Choose the menus / function that will not be displayed, and therefore cannot be changed.
P = PID Menu, C = Configuration Menu (except [`tAG]), O = Operations Menu (except [CnFG]), A = Auto-tune.
[AhyS]
[`LAt]
[`SIL]
[FAIL]
[tIM]
[Strt]
[`rdy]
[``St]
[SLOC]
[`tAg]