RM A M odule 26 Chapter 4 Setup Page
Access Module Setup Page
Display
Parameter name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Param-
eter
ID
Data
Type
& Read/
Write
[iP;F2]
[ip.F2]
Communications
IP Fixed Address Part 2
Set the IP address of this
module. Each device on the
network must have a unique
address.
0 to 255 254
- - - - - - - - - - - - 17015 uint
RWE
[iP;F3]
[ip.F3]
Communications
IP Fixed Address Part 3
Set the IP address of this
module. Each device on the
network must have a unique
address.
0 to 255 1
- - - - - - - - - - - - 17016 uint
RWE
[iP;F4]
[ip.F4]
Communications
IP Fixed Address Part 4
Set the IP address of this
module. Each device on the
network must have a unique
address.
0 to 255 1
- - - - - - - - - - - - 17017 uint
RWE
[iP;S1]
[ip.S1]
Communications
IP Fixed Subnet Part 1
Set the IP subnet mask for
this module.
0 to 255 255
- - - - - - - - - - - - 17020 uint
RWE
[iP;S2]
[ip.S2]
Communications
IP Fixed Subnet Part 2
Set the IP subnet mask for
this module.
0 to 255 255
- - - - - - - - - - - - 17021 uint
RWE
[iP;S3]
[ip.S3]
Communications
IP Fixed Subnet Part 3
Set the IP subnet mask for
this module.
0 to 255 0
- - - - - - - - - - - - 17022 uint
RWE
[iP;S4]
[ip.S4]
Communications
IP Fixed Subnet Part 4
Set the IP subnet mask for
this module.
0 to 255 0
- - - - - - - - - - - - 17023 uint
RWE
[iP;g1]
[ip.g1]
Communications
Fixed IP Gateway Part 1
0 to 255 0
- - - - - - - - - - - - 17026 uint
RWE
[iP;g2
[ip.g2]
Communications
Fixed IP Gateway Part 2
0 to 255 0
- - - - - - - - - - - - 17027 uint
RWE
[iP;g3]
[ip.g3]
Communications
Fixed IP Gateway Part 3
0 to 255 0
- - - - - - - - - - - - 17028 uint
RWE
[iP;g4]
[ip.g4]
Communications
Fixed IP Gateway Part 4
0 to 255 0
- - - - - - - - - - - - 17029 uint
RWE
[Mb;E]
[Mb.E]
Communications
Modbus TCP Enable
Activate Modbus TCP.
[``no] No (59)
[`YES} Yes (106)
Yes
- - - - - - - - 78 17041 uint
RWE
[EiP;E]
[EiP.E]
Communications
EtherNet/IP™ Enable
Activate Ethernet/IP™.
[``no] No (59)
[`YES} Yes (106)
Yes
- - - - - - - - 79 17042 uint
RWE
Note: Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User Set