Watlow EZ-ZONE RMA Modul Manual de usuario Pagina 28

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 79
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 27
Watlow EZ-ZONE
®
RM A M odule 25 Chapter 4 Setup Page
Access Module Setup Page
Display
Parameter name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Param-
eter
ID
Data
Type
& Read/
Write
gLbL]
[`Set]
Global Menu
[d;prs]
[dPrS]
Global
Display Pairs
Defines the number of Dis-
play Pairs.
1 to 10 1 - - - - 0x6A
(103)
1
0x1C (28)
- - - - 3028 uint
RWES
[USr;S]
[USr.S]
Global
User Settings Save
Save all of this controller's
settings to the selected set.
[none] None (61)
[SEt1] User Set 1 (101)
[SEt2] User Set 2 (102)
- - - -
26
0x65
(101)
1
0x0E (14)
8 1014 uint
RWE
[USr;r]
[USr.r]
Global
User Settings Restore
Replace all of this control-
ler's settings with another
set.
[none] None (61)
[SEt1] User Set 1 (101)
[SEt2] User Set 2 (102)
[FCty] Factory (31)
- - - -
24
0x65
(101)
1
0x0D
(13)
7 1013 uint
RWE
[CoM]
[`SEt]
Communications Menu
[Ad;M]
[Ad.M]
Communications
Modbus Address
Set the Modbus address.
1 to 247 1
432 0x96
(150)
2
1
76 17007 uint
RWE
[bAUd]
[bAUd]
Communications
Baud Rate
Set the speed of this con-
troller's communications to
match the speed of the serial
network.
9,600 (188)
19,200 (189)
38,400 (190)
9,600
434 0x96
(150)
2
3
74 17002 uint
RWE
[`PAr]
[ PAr]
Communications
Parity
Set the parity of this control-
ler to match the parity of the
serial network.
[none] None (61)
[EuEn] Even (191)
[`odd] Odd (192)
None
436 0x96
(150)
2
4
75 17003 uint
RWE
[M;hL]
[M.hL]
Communications
Modbus Word Order
Select the word order of
the two 16-bit words in the
floating-point values.
[hiLo] Word High Low
(1330)
[Lohi] Word Low High
(1331)
Low High
438 0x96
(150)
2
5
80 17043 uint
RWE
[iP;M]
[iP.M]
Communications
IP Address Mode
Select DHCP to let a DHCP
server assign an address to
this module.
[dhCP] DHCP (1281)
[F;Add] Fixed Address
(1284)
DHCP
- - - - - - - - 77 17012 uint
RWE
[iP;F1]
[ip.F1]
Communications
IP Fixed Address Part 1
Set the IP address of this
module. Each device on the
network must have a unique
address.
0 to 255 169
- - - - - - - - - - - - 17014 uint
RWE
Note: Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User Set
Vista de pagina 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 78 79