Watlow EZ-ZONE
®
RM A M odule 22 Chapter 3 Operations Page
Access Module Operations Page
Display Parameter Name
Description
Range Default Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[dLog]
[oPEr]
Data Logging Menu
[Stat]
[Stat]
Data Logging
Status
Status indicates the status
of the data logging function.
OK means logging can be
started or can continue. No
Memory can indicate the
memory card is full or not
present.
[no;M] No Memory (1637)
[``oH] OK (138)
- - - - 1452 0x89
(137)
1
2
50 37002 uint
R
[AME]
[AME]
Data Logging
Available Memory
Available Logging Memory
indicates the remaining
space available for logging
in kilobytes.
0 to 9,999 - - - - 1456 0x89
(137)
1
4
52 37004 uint
R
[`A;ti]
[ A.ti]
Data Logging
Available Logging Time
Available Logging Time
when logging is active, in-
dicates the remaining time
that logging can continue in
hours. When logging is not
active, indicates zero.
0 to 9,999 hours - - - - 1458 0x89
(137)
1
5
53 37005 uint
R
[bCUP]
[oPEr]
Backup Menu
[Stat]
[Stat]
Backup (1 to 6)
Status
Status indicates the status
of the configuration backup
function.
Off - means no backup or re-
store action is running.
Save - indicates the con-
figuration of a zone is being
saved to backup memory.
Restore - indicates a saved
configuration is being re-
stored to a zone.
Monitor - When backup is
set to restore on a change
the RMA will check to see if
a module serial number has
changed. If so, a restore will
take place for that module.
Complete - indicates that
the restoration is complete.
Error - indicates that the
last action failed.
[`oFF] Off (62)
[saue] Save (1644)
[rest] Restore (1645)
[mon] Monitor (1187)
[Cplt] Complete (18)
[`err] Error (28)
Off 1274 0x8A
(138)
1 to 6
3
60 38003 uint
R
Note: Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User Set