[`tA9] = [P```]
0°F or 0°C
[-999] [9999]
[-9(9] [99(9]
Select a value,
adjustable between
-999° and 9999°F or C
or -99.9° and 999.9°F or
C to eliminate a
difference between the
displayed temperature
and the actual
temperature.
[`CAL]
Calibration Offset
[`tA9] = [P```];
or if
[Pb`h] = 0;
or if
[Pb`h] is hidden; and
if [Pb`c] = 0;
or if
[Pb`c] is hidden
0 minutes
[`)00] [`(99]
Select a value,
adjustable between 0.00
and 9.99 minutes.
[``dE]
Derivative Function
[`tA9] = [P```];
or if
[Pb`h] = 0;
or if
[Pb`h] is hidden; and
if [Pb`c] = 0;
or if
[Pb`c] is hidden
5.00 minutes/repeat
[``)0] [9(99]
Select a value,
adjustable between 0.0
and 99.99
minutes/repeat.
[``It]
Integral Function
[`tA9] = [P```];
or if
[Pb`c] = 0
or if
[Pb`c] is hidden
5.0 seconds
[``)1] [`6)0]
[``%0] [`6)0]
Select a value between
0.1 and 60.0 seconds
(Solid-State Relay or
Switched DC) or 5.0 and
60.0 seconds
(Electromechanical
Relay).
[Ct`c]
Cycle Time Cool
54 Watlow Series 935A User’s Manual
PID Menu
Prompt Range Default Hidden if * Your Settings